Bradford White BLMC125NA User Manual

Page 36

Advertising
background image

Page 34

Bradford White Corp.

11.2.4 Flame Sensor

The flame sensor is a single rod system. To replace

the flame sensor electrode, shut off the 120 Volt power

supply to the boiler. Turn off all manual gas valves

connecting the boiler to the main gas supply line.

Remove the front door of the boiler to gain access to the

flame sensor electrode. Remove the flame sensor wire

from the electrode. Remove the two bolts fastening the

electrode to the burner doors. Remove and replace the

old flame sensor gasket. Reinstall a new flame sensor

electrode in the reverse order if the old electrode is

determined defective.

Caution

Igniters and sensors get hot and

can cause burns or injury.

11.2.5 Blower

The combustion air blower is a high-pressure

centrifugal blower with a variable speed motor. Speed

of the motor is determined by the control logic. 120

Volts remain on to the blower at all times. If a blower

change is required, turn off the 120 Volt power and gas

supply to the unit. Take the front panel off. Disconnect

the 120 Volt and control signal connections from the

blower. Disconnect the bolts connecting the venturi to

the blower housing. Disconnect the fan outlet bolts from

the burner door blower arm. If the fan is determined

to be defective replace the existing fan with a new one

reversing the steps above. Make sure to install all of the

required O-rings and gaskets between the blower arm

and the blower and blower face and venturi flange.

11.2.6 Heat Exchanger Coils

Black carbon soot buildup on the external surfaces

of the heat exchanger is caused by one or more of the

following; incomplete combustion, combustion air

problems, venting problems and heater short cycling.

Soot buildup or other debris on the heat exchanger may

restrict the flue passages.

If black carbon soot buildup on the heat exchanger

is suspected, disconnect electrical supply to the unit,

and turn off the gas supply by closing the manual gas

valve on the unit. Access the heat exchanger through

the burner door at the front of the boiler, and inspect the

tubing using a flashlight. If there is a buildup of black

carbon soot or other debris on the heat exchanger, clean

per the following:

Caution

Black carbon soot buildup on a dirty heat exchanger

can be ignited by a random spark or flame. To prevent

this from happening, dampen the soot deposits with

a wet brush or fine water spray before servicing the

heat exchanger.

1. Shut off the 120 Volt power supply to the boiler

2. Turn off all manual gas valves connecting the

boiler to the main gas supply line.

3. Remove the four bolts connecting the blower

flange to the burner door arm.

4. Remove the nuts located on the outside diameter of

the burner door to the heat exchanger.

5. Remove the burner door/burner assembly from the

heat exchanger.

6. Disconnect the condensate drain line.

7. Attach a longer hose to drain and run to a bucket.

8. Clean the heat exchanger by brushing light

accumulations of soot and debris. Use a brush

with soft bristle (non metal) to avoid damaging the

surface of the heat exchanger tubes.

9. Once the tubes have been brushed clean rinse

the tubes and combustion chamber with a small

amount of water to rinse all of the debris out of

the bottom of the flue collector and into the longer

condensate trap line, which is being diverted into a

separate container.

NOTE: The Warranty does not cover damage caused

by lack of required maintenance, lack of water flow,

or improper operating practices.

WARNING

Failure to rinse the debris from the heat exchanger

and temporary drain line may lead to clogged

condensate lines, traps and neutralizers. Condensate

pumps (if used) may also be damaged from the

debris left behind, possibly causing property damage.

11.

Install all components removed in

the reverse order to place the appliance back in

operation. Make sure all gaskets are in place as

components are installed. Replace any damaged

gaskets. Do NOT reuse damaged gaskets.

12. Place the appliance in operation according to

Section 10

checking all gas connections for leaks.

Confirm all fasteners are tight.

11.2.7 Gas Conversion

Brute Elite units can be converted from natural

to propane gas or from propane to natural gas easily

in the field. If a gas conversion is performed, the unit

must be identified with the appropriate gas labels and

a conversion sticker to allow technicians performing

maintenance in the future to properly identify the gas

type of the appliance. These stickers are included with

the boiler during shipment.

WARNING

This conversion shall be installed by a qualified

service agency in accordance with the manufacturer's

instructions and all applicable codes and

requirements of the authority having jurisdiction. If

the information in these instructions is not followed

exactly, a fire, an explosion or production of carbon

monoxide may result causing property damage,

personal injury or loss of life. The qualified

service agency is responsible for the proper and

complete installation of this kit. The installation is

Advertising