1 gas supply and piping – Bradford White BLMC125NA User Manual

Page 16

Advertising
background image

Page 14

Bradford White Corp.

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY

UNDILUTED PROPANE

NOMINAL PIPE SIZE

@

11" W.C. INLET AND 0.5" W.C. PRESSURE DROP

SIZE

1/2"

3/4"

LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER
HOUR

20

200 418

40

137

287

60

110 231

80

94

197

100

84

175

NOTES: 1. Follow all local and national LP gas codes for line sizing and

equipment requirements. 2. Verify that inlet gas pressure remains between

4 and 13 inches of water column before and during operation.

Source: ANSI Z223.1-80 National Fuel Gas Code.

Table 6D.

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS

NOMINAL PIPE SIZE

@

0.30" W.C. PRESSURE DROP

LENGTH

1/2"

3/4"

FT

CUBIC FEET OF GAS PER HOUR

20

92 190

40

130

60

105

80

90

100

Table 6C.

Brute Elite NATURAL GAS REQUIRED

SIZE

CU FT / HR.

125 125

TO SIZE PIPING:

Measure linear distance from meter outlet to last boiler. Add total input

of all boilers and divide by 1000 to obtain cu ft / hr required. Add total

equivalent length of fittings used according to Table 6B. Align total

length (pipe and fittings) on left side column of Table 6C with highest

cubic feet of gas required.

Notes:

Consult and confirm with Applicable Fuel Gas Code before beginning

work. Verify gas inlet pressure is between 4 and 13 in W.C. before

starting boiler.

Table 6A.

SECTION 4.

Gas Supply and Piping

4.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not the appliance.

Review the following instructions before

proceeding with the installation.
1. Verify that the appliance is fitted for the proper type

of gas by checking the rating plate. Brute Elite will

function properly without the use of high altitude

modification at elevations up to 10,000 feet (3050

m).

2. The maximum inlet gas pressure must not exceed

13" W.C. (3.2kPa). The minimum inlet gas

pressure is 4" W.C. (1.0kPa).

3. Refer to

Tables 6A, 6B, 6C and 6D

to size piping.

4. Run gas supply line in accordance with all

applicable codes.

5. Locate and install manual shutoff valves in

accordance with state and local requirements.

6. A sediment trap must be provided upstream of the

gas controls.

7. All threaded joints should be coated with

piping compound resistant to action of liquefied

petroleum gas.

8. The appliance and its individual shutoff valve must

be disconnected from the gas supply piping during

any pressure testing of that system at test pressures

in excess of 1/2 PSIG (3.45kPa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than

1/2 PSIG (3.45kPa).

10. The appliance and its gas connection must be leak

tested before placing it in operation.

11. Purge all air from gas lines.

WARNING:

Open flame can cause gas to ignite and result in

property damage, severe injury, or loss of life.

NOTE: The Brute Elite appliance and all other gas

appliances sharing the gas supply line must be firing at

maximum capacity to properly measure the inlet supply

pressure. The pressure can be measured at the supply

pressure port on the gas valve. Low gas pressure could

be an indication of an undersized gas meter, undersized

gas supply lines and/or an obstructed gas supply line.

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING

1/2"

3/4"

1"

LINEAR FEET

90° ELBOW

3.6

4.4

5.2

TEE

4.2

5.3

6.6

Table 6B.