Bradford White BLMC125NA User Manual

Page 39

Advertising
background image

Page 37

The Brute Elite 125

was reached

however the cycle count will

not

increment

any

higher

than 999,999 cycles

Replace controller or adjust the count using blue display

50 Maximum hours count

Control operates correctly,

was reached

however the hours count will

not

increment

any

higher

than 999,999 hours

248

CH

outdoor

temperature

was invalid

251 CH ODR max outdoor temp-

Confirm outdoor reset

erature setpoint was invalid

settings. An invalid

252 CH ODR min outdoor temp-

adjustment has been

erature setpoint was invalid

made

253 CH ODR min water temp-

erature setpoint was invalid

254 CH ODR temperature range

Increase Outdoor air temp-

Adjust setting to within appropriate range

was too small

erature min and max values

(min. 12°C / 22°F)

to a difference greater than

22°F (12°C)

255 CH setpoint minus ODR

Increase Outdoor water

min water temperature was

temperature min and max

too small (min. 12°C / 22°F)

values to a difference greater

Increase setpoint or

than 22°F (12°C)

decrease min water temp.

565 Heat exchanger T-rise limit

Heat exchanger temperature Check for correct water flow

was exceeded

rise exceed

MISCELLANEOUS

Boiler will not stay lit

Indicates lack of flame signal, Check flame detector wiring; clean / replace flame

check fault code on display

detector

Boiler bangs, knocks, hisses

Insufficient water flow /

Check for proper flow, follow piping guidelines in

pump failure; improper piping manual; replace pump; improper glycol percentage

(see Section 6)

Flame pulsates, venting

Insufficient / improper

Ensure venting complies with

Section 3

noise or has difficulty lighting

venting; dirty burner; air in

gas line; dirty heat exchanger

Table 14. Error Codes.

CODE# PROBLEM

PROBABLE CAUSE

SOLUTION

ALERT CODES