SECTION 11.

Maintenance

WARNING

Disconnect all power to the appliance before

attempting any service to the appliance. Contact with

electricity can result in severe injury or death.

11.1 System Maintenance

(yearly, unless otherwise noted)

1. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.

2. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean the

screens in the vent terminal and combustion air

terminal (when used).

3. Keep the appliance area clear and free from

combustible materials, gasoline, and other

flammable vapors and liquids.

4. If the appliance is not going to be used for

extended periods in locations where freezing

normally occurs, it should be isolated from the

system and completely drained of all water.

5. Low water cutoffs, if installed, should be checked

every year. Float type low water cutoffs should be

flushed periodically.

6. Inspect and clean the condensate collection system

yearly.

7. When a means is provided to neutralize

condensate, ensure that the condensate is being

neutralized properly.

8. Removal of burner door and inspection of

combustion coil and flue passages is required

at least once a year. Clean with a soft bristle

brush / vacuum or wash with water if necessary.

Sooting and buildup on the coils is an indication of

improper set up and poor combustion. Determine

the cause and make corrections.

9. Inspect the vent system and air intake system, and

ensure that all joints are sealed properly. If joints

need to be resealed, completely remove existing

sealing material, and clean with alcohol. Apply

new sealing material, and reassemble.

11.2 Appliance Maintenance and

Component Description

Use only genuine Bradford White replacement parts.

Caution

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and danger-

ous operation. Verify proper operation after servicing.

Brute Elite gas and electric controls are engineered

for long life and dependable operation, but the safety of

equipment depends on their proper functioning. Only

a qualified service technician should inspect the basic

items listed below every year:

a. Appliance control

f. Flow switch

b. Automatic gas valve

g. Low water cutoff

c. Pressure switches

h. Burner

d. Blower

i. Heat exchanger

e. Pump

11.2.1 Burner

Check the burner for debris. Remove the blower

arm assembly to access the burner. Remove the 4 bolts

connecting the blower to the arm (

see Figure 32

).

Remove the 5 bolts, which hold the burner arm in place.

Pull burner up and out. Clean burner, if necessary, by

blowing compressed air from the outside of the burner

into the center of the burner, and wipe the inside of the

burner clean with glass cleaner. A dirty burner may be an

indication of improper combustion or dirty combustion

air. Determine the cause, and correct. If damaged,

replace the burner gasket when replacing the burner.

NOTE: When installing the burner, make sure the flange

is aligned with the mating surface, as each is keyed to

control fit.

11.2.2 Appliance Control

Brute Elite has an integrated control that

incorporates manual reset high limit control, operating

temperature control, modulating control, ignition

control, outdoor reset control, pump control and many

other features. If any of these features are thought

to be defective, please consult the factory for proper

trouble shooting practices prior to replacing the control.

If control replacement is required, turn off all power

to the appliance and shut off all manual gas valves to

the appliance. Remove the front door to the appliance

and the control panel plastic bezel. Remove all wire

connections from the control board. The control board

connections are keyed to only allow connection in the

proper location, but proper handling techniques should

be used to avoid damage to the wiring or connectors. To

remove the control push in on the two tabs on the left

side of the board to unlatch the clips from the control

panel. Rotate the control around the fastening points

on the right side of the control to remove the hooks

from the control panel. To replace the control repeat the

steps above in the reverse order making sure to connect

all wires in the proper location. Place the appliance in

operation following the steps outlined in

Section 10

.

11.2.3 Ignitor Assembly

The ignitor assembly is a two rod system that

consists of a ground rod and a sense rod. To remove the

ignitor assembly, shut off the 120 Volt power supply to

the appliance. Turn off all manual gas valves connecting

the appliance to the main gas supply line. Remove the

front door of the boiler to gain access to the ignitor

assembly. Remove the two wires connected to the

assembly. Then remove the two bolts connecting the

ignitor assembly to the burner door. Remove and replace

the old ignitor assembly gasket. Reinstall a new ignitor

assembly in the reverse order if the old assembly is

determined defective. Replace gasket if necessary.