Bradford White BLMC125NA User Manual

Page 28

Advertising
background image

Page 26

Bradford White Corp.

SECTION 8.

Control Setup and Operation

The Brute Elite control is an integrated electronic

control that replaces many of the individual components

found on older appliances. The control acts as the

ignition control, pump control, high limit and cascading/

lead lag control and is setup using the digital display on

the appliance.

8.1 Digital Display Navigation

The Digital Display is centered in the middle of

the User Interface and has 3 seperate modes of control.

They are USER, SETUP and DIAGNOSTIC. The names

of these modes clearly labels the intent of the different

levels of control. A USER might be the homeowner or

a service technician. SETUP displays all the controls

needed when setting up or expanding the boiler. And

DIAGNOSTIC is intended for a trained Brute Elite

technician. The menu structure and variables in each are

shown in

Table 9, Table 10, and Table 11

.

USER Mode is the home screen shown on the

control. If the display is not in USER Mode wait for the

display timeout period to be reached or press the Done

button to return to the USER Mode.

SETUP Mode is accessed by holding the up and

down arrow keys simultaneously for 3 seconds.

DIAGNOSTIC Mode is accessed by holding the

NEXT button for 3 seconds

Once in a particular Mode, navigation consists of

pressing the next button to scroll from item to item and

then pressing the up and down arrows to change values.

Once the value is adjusted, the NEXT or DONE button

can be pressed.

Figure 23. The

USER INTERFACE

.

MENU ITEM

DEFINITION

F or C

Selects temperature units

LBTHODLOD Outdoor reset enable/disable -

enables menu items

LBT

Low boiler setpoint during outdoor reset

HOD

High outdoor temperature setpoint

LOD

Low outdoor temperature setpoint

RMT Add

Used for Lead/Lag (follow menus)

LL

Lead/Lag enable/disable - enables menu items

HS

Hysteresis - temp range between on/off cycles

bL

Base Load % - input rate before next boiler fires

Sd

Warm weather shut-down temperature

ASC

Anti short cycle - minutes of delay between

startup
bAC

Future use - Press DONE to exit menu.

PAS

Future use - Press DONE to exit menu.

NOTE:

When enabling/disabling functions, select "Done" and wait 30

seconds before scrolling.

Table 10. SETUP Mode Parameters.

MENU ITEM

FUNCTION

RANGE

DEFAULT

Outlet water Displays the current outlet 55-180°F 120°F

temperature water temperature & allows

the setpoint to be adjusted

Inlet water

Displays the current inlet

temperature water temperature
Delta T

Displays the current

temperature rise across

the heat exchanger

Stack

Displays the current stack

temperature temperature
Outdoor

Displays the current outdoor

temperature air temperature
Firing Rate Displays an indicator of the

current firing rate based

upon fan RPM. The actual

firing rate may vary.

Table 9. USER Mode Menu.

MENU ITEM

DESCRIPTION

mA

Display the flame sense signal

Alert codes

Displays the current alert code

Lockout code

Displays the current lockout code

Outlet limit

Displays outlet temperature limit

DHW limit

Displays Domestic Hot Water limit setting

DHW actual

Displays Actual DHW temperature

Stack limit

Displays

Stack limit setting

Min. firing rate Displays the minimum firing rate allowed
Min. forced

Allows the user to force the boiler to fire at

firing rate

the minimum firing rate

Max forced

Allows the user to force the boiler to fire at

firing rate

the maximum firing rate

Rate indicator Displays a indicator of the firing rate based

off of the fan RPM. Actual firing rate may

vary depending upon setup.

Table 11. DIAGNOSTIC Mode Menu.