Bradford White BLMC125NA User Manual

Page 29

Advertising
background image

Page 27

The Brute Elite 125

8.2 Ignition Control- Sequence of Events

1. Call for heat

2. Safety chain check

3. Fan starts.

4. Prepurge timer is started.

5. Pre ignition time of 2 seconds to check the flame

sensor operation and status.

6. Trial for ignition period, 4 seconds. The direct

spark ignition switches to constant spark for three

seconds, during which time the gas valve is open.

For the last second of the ignition period direct

spark is de-energized and the flame sensor checks

for established flame. If flame is sensed the control

enters "Run" to satisfy the demand. If flame is

not established the control enters a retry, starting

from step 2. If flame has not been established in

the appropriate number of retries the control will

lockout with a 109 error code.

7. Call for heat complete

8. Gas valve off

9. Fan and pump over run times active to purge the

system
The sequence is the same for DHW or Central

Heat modes. Upon a call for Central Heat, the 3-way

valve will shift position, allowing boiler water to enter

the building's heating loop.

8.3 Modulation Control

The control uses a PID algorithm to adjust

the firing rate of the boiler as the control point is

approached. The goal of the control is to operate

at a minimum firing rate to match the load on the

appliance. The burner modulates to achieve the setpoint

temperature, away from the actual off point.

8.4 Pump Control

The boiler pump is active anytime there is a call

for heat applied to the control. When there is a central

heat call supplied the system pump relay is active. If

there is a DHW call supplied while the central heat

call is active the system pump turns off. This happens

because of domestic hot water priority, which forces the

control to satisfy the domestic water demand prior to the

hydronic demand. When the last heat demand is satisfied

the boiler pump enters an overrun time.

8.5 High Limit

The control uses a dual thermistor sensor to

monitor the Brute Elite's maximum temperature. The

high limit sensor is installed in the outlet water. A dual

thermistor sensor is used, so that the two temperatures

can be monitored and compared to confirm accuracy.

The control will automatically reduce the firing of the

Brute Elite to prevent the high limit from tripping. The

high limit setpoint is not adjustable.

8.6 Stack Temperature

The stack temperature is a dual thermistor sensor

and is limit rated. The control compares each of the

temperature readings to determine accuracy. The stack

sensor is used as a limiting feature to avoid excessive

temperatures in the venting.

8.7 Domestic Hot Water Temperature

The domestic hot water temperature sensor is used

to control DHW temperature. The DHW setpoint can be

adjusted through the USER menu structure.

DHW setpoint is displayed during DHW mode.

For BLMH model, an aquastat will be used in lieu of a

sensor to control temperature of an indirect tank.

8.8 Lead Lag / Cascading

Lead Lag/Cascading allows multiple boilers to be

connected together and controlled from one common

sensor input. Up to 8 boilers can be connected together

in a single system. To setup Lead/Lag or cascading

operation there are several settings in the "setup"

menu structure that must be adjusted for the specific

installation, each is covered in the following sections.

8.8.1 Lead Lag Setpoint

The lead lag setpoint is set from the "user"

menu using the "LL" variable. This is the temperature

the boiler is attempting to maintain at the system

sensor. This setting doesn't control the boiler outlet

temperature, so the water temperature at the boiler

outlet may be much hotter than the system temperature

setpoint. Adjust the LL setpoint to the desired operating

temperature of the system.

8.8.2 Lead Lag Master/Slave Selection

In the SETUP menu structure, the "LL" menu

allows the lead lag system to be turned on and the boiler

to be configured as a master or slave control. In each

lead lag system there can only be one master control, so

proper selection is important to avoid operating issues.

To set the boiler to lead lag "master" operation the LL

menu should be set to "LDR". To set the boiler to slave,

"SLA" should be selected.

8.8.3 Lead Lag Address

The Lead Lag address must be set for each boiler

connected to the lead lag system. Each boiler must

have a unique address selected for the system to work

properly. Typically, the lead or master boiler should be

set to address one and the remaining boilers should be

set to values 2–8 depending upon how many boilers are

installed in the system.

8.8.4 Lead Lag Hysteresis

The lead lag system uses a hysteresis value set

in the setup menu, called, "HS". The hysteresis and

setpoint values control the on and off points of the

boiler. If the lead lag setpoint is adjusted to 120°F with

a hysteresis value of 5°F the boiler will turn off when

the water temperature reaches 125°F and will turn back

Advertising
This manual is related to the following products: