The Brute Elite 125

4. Brute Elite will enter the start sequence. Blower

and pump will energize for pre-purge, then the

ignition sequence starts. After all safety devices

are verified, the gas valve opens. If ignition doesn’t

occur, turn off the Brute Elite, check that there is

proper gas supply. Wait 5 minutes and start the unit

again.

5. Turn Brute Elite on.

6. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested:

(a) Close gas shutoff valve with burner

operating.

(b) Flame will go out and blower will continue

to run for the post purge cycle. One or three

additional attempts to light will follow

including pre-purge, ignitor on, valve/flame

on and post purge. Ignition will not occur

as the gas is off. The ignition control will

lockout.

(c) Open gas shutoff valve. Reset the boiler

control by pressing the

RESET

button on

the control or on the display. Restart the

appliance. The ignition sequence will start

again and the burner will start. The appliance

will return to its previous mode of operation.

Caution

Should any odor of gas be detected, or if the gas

burner does not appear to be functioning in a normal

manner, CLOSE MAIN SHUTOFF VALVE. Do not

shut off switch. Contact your heating contractor, gas

company, or factory representative.

10.2.2 Boiler Setup and Adjustment

1. Measure the CO

2

in the flue products at high fire.

The Brute Elite can be forced to high fire to allow

for easier setup. Refer to

Section 8.1, Table 11

for instructions on how to access the forced rate

menu. The CO

2

readings should be between the

range shown in

Table 13

. If the CO

2

is not within

the range shown, adjustments may be made.

To adjust the high fire CO

2

, locate the high fire

adjuster screw according to the appropriate figure.

Slowly make adjustments in 1/16 of a revolution

increments until the CO

2

is within the range

identified.

2. Measure the CO

2

in the flue products at low fire.

Brute Elite can be forced to low fire to allow for

easier setup. Refer to

Section 8.1, Table 11

for

instructions on how to access the forced rate menu.

CO

2

readings should be between the range shown

in

Table 13

. If the CO

2

is not within the range

shown, adjustments may be made. To adjust the

low fire CO

2

, locate the low fire adjuster screw

according to the appropriate figure. Slowly make

adjustments in 1/16 of a revolution increments

until the CO

2

is within the range identified

(see

Figure 25

).

3. Repeat steps 1 and 2 to confirm that the CO

2

ranges are within the required ranges. High and

Low Fire CO2 settings should be approximately

equal. Adjust if necessary.

If any your CO2 readings

cannot be adjusted

to the specified ranges (see

Table 13)

, please

consult the factory for further information.

10.2.3 Manifold Pressure Check

1. Remove the cap that covers the manifold pressure

screw (See

Figure 25)

. Loosen the manifold pressure

screw one revolution, and attach manometer.

2. Check Manifold pressure at high fire using

manometer (see

Table 13

for pressure range).

3. When finished, remove manometer, tighten screw,

and replace the cap.

If your pressure reading is not within the

specified range (see

Table 13)

, please consult the

factory for further information.

WARNING

Improper adjustment may lead to poor combustion

quality, increasing the amount of carbon monoxide

produced. Excessive carbon monoxide levels may

lead to personal injury or death.

10.3 Shutting Down Brute Elite

1. Turn off the main electrical disconnect switch.

2. Close all manual gas valves.

3. If freezing is anticipated, drain Brute Elite and be

sure to also protect building piping from freezing.

All water must be removed from heat exchanger

and condensate trap or else damage from freezing

may occur.

This step to be performed by a qualified service person.

10.4 To Restart Brute Elite

If drained, follow

Section 10.1

in this manual

for proper filling and purging.

1. Turn off the main electrical disconnect switch.

2. Close all manual gas valves.

3. WAIT FIVE (5) MINUTES.

4. Set the aquastat or thermostat to its lowest setting.

5. Open all manual gas valves.

6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).

7. Set the temperature controller to the desired

temperature setting and switch on electrical power.

8. Burner will go through a prepurge period and

ignitor warm-up period, followed by ignition.