Page 29

The Brute Elite 125

water temperatures. The boiler setpoint is used to limit

the maximum water temperature leaving the boiler only.

The modulation rate is controlled by a 4-20mA (0-

10Vdc using converter) signal supplied by an external

control. When setting up a system using an external

control care must be taken to set the external control

algorithms to prevent the boiler from short cycling or

"hunting " to prevent premature component failure.

NOTE: A call for DHW will override external control.

9.4 Hydronic Heating Using Local Lead-

Lag/Cascading Feature

When using single or multiple Brute Elite's in lead-

lag configuration, the system sensor is used to monitor

the demand and modulation rates of the operating

system (see

Section 7

for wiring instructions).

Let’s consider the following example:

Three Brute Elite boilers (let’s call them “Lead”,

“Slave1” and “Slave2”) tied together via Modbus

1 connection, with appropriate RMT Address (1, 2,

3). System sensor input is used to indicate common

secondary loop temperature.

System setpoint = 150°F

HS (hysteresis) = 10°F (default)

BL (base load) = 50% (default)

Anti-short-cycle = 5 minutes
Run sequence is initiated when system temperature

falls to 140°F (setpoint less hysteresis value). Lead

boiler will start. All firing rates will depend on several

application characteristics, including flow rate, system

load, water volume, etc. Boilers will start at a rate of

35%. If the load is such that Lead’s rate increases to

50%, “Slave1” will go through its startup sequence and

begin firing at 35%. At this point, both boilers (Lead and

Slave1) will continue to respond simultaneously to the

load/system characteristics, by modulating up or down

together, in relation to the relative system setpoint and

load characteristics.

Scenario 1: If the system loop temperature rises quickly,

and moves above setpoint, then the boilers will

Figure 24. Outdoor Reset Setpoint Temperatures.

simultaneously drop their firing rate. If when

reaching the point where both boilers drop toward

their minimum firing rate (20%), then the first

slave will drop out. Slave1 will remain unavailable

until its ASC timer has expired (5 minutes). If

the load were to increase such to drive all active

boilers to 50% firing rate or more, during the ASC

time, Slave2 will begin its startup sequence and

begin to fire at 35%, etc.

Scenario 2: If the system loop temperature continues

to drop (load increases), then the two boilers will

increase firing rate together. At 50%, Slave2 will

begin its firing sequence and be added to the group.

All three boilers will continue to fire simultaneously at

equal input rates or…

1. Modulation rate approaches minimum firing rate

(20%), in which case Slave2 will first drop out, and

then Slave1, accordingly.

2. System temperature reaches 10°F (HS- hysteresis

value) above setpoint (e.g. 160°F), in which case

remaining boiler will shut off.

3. Any of the boilers approach its high limit

temperature the individual boiler will modulate

back.

9.5 Warm Weather Shutdown

Warm weather shutdown overrides a central

heat call for heat when the outdoor air temperature is

greater than the warm weather shutdown setpoint. Warm

weather shutdown is always active whenever there

is an outdoor sensor attached to the control. To avoid

warm weather shutdown the warm weather shutdown

temperature should be increased as necessary. The warm

weather shutdown setpoint can be adjusted in SETUP

mode, using the SD menu.

9.6 Domestic Hot Water Demand

For Combi (BLMC), DHW demand is triggered

by a flow switch located near the DHW cold water

inlet. When water begins to flow (open faucet, shower,

etc.), the boiler will fire, based on the water temperature

requirements. It may cycle on and off under very low

flow rates. Minimum flow is 0.5 gpm.

For BLMH, an optional indirect water heater can

be piped-in using Brute Elite's integral 3-way valve as

a zone valve. An aquastat in the indirect water heater

connected in place of the flow switch will signal demand

for DHW. The service person should note the minor

wiring differences on

Figure 22

.