For documentation and a better overview of the device settings, we recommend that you fill
in this configuration overview before setting the device parameters (link to form, see "Cre-
ate configuration overview" chapter).

Select Inputs

The parameter sets are selected via the 4 select inputs SEL1 (Y10), SEL2 (Y11), SEL4
(Y12), SEL8 (Y13). Only one of the configured parameter sets can be selected.
One of the following modes can be selected in the "Select inputs mode" menu, depending
on the application:
"None" mode
For applications up to PL e of EN ISO 13849-1 and SIL CL 3 of EN IEC 62061.
The select inputs are ignored. Only the parameter set P0 is configured and used. The low-
est frequency (10 mHz) is automatically set for all other parameter sets.
"1 from 4" mode
For applications up to PL e of EN ISO 13849-1 and SIL CL 3 of EN IEC 62061.
A maximum of 4 parameter sets can be configured and used: P1, P2, P4 and P8.