3 examples, 1 connection of proximity switch, 1 features – Pilz PNOZ s30 24-240VACDC 2 n/o 2 n/c User Manual

Page 83: 2 configuration overview, Examples, Connection of proximity switch

Advertising
background image

Supplementary data

Operating Manual PNOZ s30
1001715-EN-13

83

Examples

Connection of proximity switch

Features
PNOZ s30

}

Standstill monitoring for enabling the safety gate via Rel. 1:

Standstill is detected at <= 2 Hz, the output Rel. 1 switches on and the safety gate can
be released with the pushbutton S3.

}

Monitoring for overspeed via Rel. 2:

Overspeed is detected at >= 500 Hz and the output Rel. 2 switches off.

}

Feedback loop monitoring for Rel.1 via feedback loop input Y1,

Feedback loop monitoring for Rel.2 via feedback loop input Y2

}

Automatic reset

Encoder

The measured values are detected by two proximity switches (pnp).
PNOZ s4

}

Safety gate monitoring

Configuration overview

9.3