3 basic settings for the rotary encoder – Pilz PNOZ s30 24-240VACDC 2 n/o 2 n/c User Manual

Page 45

Advertising
background image

Commissioning

Operating Manual PNOZ s30
1001715-EN-13

45

}

Output assignment
– Standstill: Relay output Rel. 1 and semiconductor output Out 1
– Speed: Relay output Rel. 2 and semiconductor output Out 2

}

Reset mode
– Rel. 1, Rel. 2 Out 1, Out 2: Automatic reset

}

Switch delay

None

}

Max. encoder frequency

3.5 kHz

Basic settings for the rotary encoder
Settings for basic configuration 2

Level

Indication
on the display

Description

Settings

1

Load Basic Parame-

ter
Encoder:
Default:
Load?

Select the default settings with

which the basic configuration

menu "Rotary encoder" is to be

called:
-

Load: The basic parameters are

loaded. Switches afterwards to the

basic menu "Rotary encoder".
The basic parameters should al-

ways be loaded when commis-

sioning for the first time.
-

Edit: The basic parameters are

not loaded, i.e. all parameters are

retained. The basic menu parame-

ters can be changed within the

permitted boundaries.
-

ESCAPE: Exits the basic menu.

2

Encoder
Default:
TTL
differential

Select rotary encoder type

-TTL differential (A, /A, B, /B)
-TTL single ended (A, B)
-HTL differential (A, /A, B, /B)
-HTL single ended (A, B)
-sin/cos 1 Vss (A, /A, B, /B)
-Hiperface (A, /A, B, /B)

2

Standstill
Rel.1 Out 1
Default:
100 Hz

Enter standstill frequency

10 mHz to 1.00 kHz

2

v max:
Rel.2 Out 2
Default:
5.00 kHz

Enter the max. permitted speed

10 mHz to 1.00 MHz

6.2.6.3

Advertising