Commissioning

Operating Manual PNOZ s30
1001715-EN-13

30

Commissioning

Wiring

General wiring guidelines

Note:

}

Information given in the "Technical details" must be followed.

}

Use copper wire that can withstand 75 °C.

}

The cable used to connect the rotary encoders and the proximity switches must be

shielded (see connection diagrams in the chapter entitled "EMC-compliant wiring").

}

The shield may only be connected to earth at a single point.

}

Earth loops should be avoided.

}

If possible, the connections for the various earth potentials (GND, S21, Y30 und A2)

should not be connected on the PNOZ s30 but should be connected directly to the
GNDs on the connected units, otherwise noise susceptibility may be increased signifi-
cantly (conductor loops are not permitted).

Pin assignment of RJ45 socket

RJ45 socket
8-pin

PIN

Track

8 1

1

S

2

GND

3

Z

4

A

5

/A

6

/Z

7

B

8

/B

Supply voltage

Supply voltage

AC

DC

A1

L1

N

A2

A1

L+

A2

L-

6

6.1

6.1.1

6.1.2

6.1.3