Chapter 6 - Troubleshooting & Maintenance

97

6.7 Daily and Periodic Inspection Items

Period

Inspection

Location

Inspection

Item

Inspection

Daily

1 year

2 year

Inspection Method

Criterion

Measuring

Instrument

Ambient
Environ-

ment

Is there any dust?
Is the ambient temperature and
humidity adequate?

Ο

Refer to the precautions

Temperature:
-10~+40 no
freezing.

Humidity: Under
90% no dew

Thermometer,
Hygrometer,
Recorder

Equipment Is there any abnormal oscillation

or noise

Ο

Use sight and hearing

No abnormality

All

Input

Voltage

Is the input voltage of the main

circuit normal

Ο

Measure the voltage between

the terminals R, S, T

Digital

Multi-

Meter/Tester

All

Megger check (between the main
circuit and the ground)

Are any fixed parts removed?
Are there any traces of
overheating at each component’s

cleaning?

Ο


Ο

Ο



Ο

Undo the inverter connections
short the terminals R, S, T, U,

V, W and measure between
these parts and the ground.
Tighten the screws.

Visual check.

Over 5MΩ
No fault

DC 500V
class Megger

Conductor/

Wire

Is the conductor rusty?

Is the wire coating damaged?

Ο

Ο

Visual check

No fault

Terminal

Is there any damage?

Ο Visual check

No fault

IGBT

Module

/Diode

Module

Check the resistance between
each of the terminals.

Ο Undo the inverter connection

and measure the resistance
between R, S, T ⇔ P, N and
U, V, W ⇔ P, N with a tester.

(Refer ‘How to
Check Power
Components”)

Digital Multi-
Meter/Analog
Tester

Smoothing

Capacitor

Is there any liquid coming out?
Is the safety pin out, and is there
any swelling?

Measure the capacitance.

Ο


Ο


Ο

Visual

check.

Measure with a capacitance-
measuring device.

No fault
Over 85% of the
rated capacity

Capacitance
Measuring
Device

Relay

Is there any chattering noise
during operation?

Is there any damage to the
contact

Ο


Ο

Auditory

check.

Visual check.

No fault

Main Cir

cuit

Resistor

Is there any damage to the
resistor insulation?
Is the wiring in the resistor

damaged (open)?

Ο


Ο

Visual

check.


Disconnect one of the

connections and measure
with a tester.

No fault
Error must be
within ±10%
the displayed
resistance

Digital Multi-
Meter/Analog
Tester

Contr

ol Cir

cuit

Pr

otective Cir

cuit

Operation

Check

Is there any unbalance between
each phases of the output

voltage?

Nothing must be wrong with

display circuit after executing the
sequence protective operation

Ο




Ο

Measure the voltage between
the output terminals U, V and

W.

Short and open the inverter

protective circuit output.

The voltage
balance between

the phases for
200V (800V)
class is under

4V (8V).
The fault circuit

operates
according to the
sequence.

Digital Multi-
Meter/Rectifyi

ng Voltmeter