Chapter 4 - Parameter Description [FU2]


50

4.3 Function 2 Group [FU2]

FU2-00: Jump to Desired Code #





Jumping directly to any parameter code can be
accomplished by entering the desired code
number.

FU2-01: Previous Fault History 1
FU2-02: Previous Fault History 2
FU2-03: Previous Fault History 3
FU2-04: Previous Fault History 4
FU2-05: Previous Fault History 5
FU2-06: Erase Fault History

















This code displays up to five previous fault (trip)
status of the inverter. Use the [FUNC], [

▲] and [▼]

key before pressing the [RESET] key to check the
fault content(s), output frequency, output current,
and whether the inverter was accelerating,
decelerating, or in constant speed at the time of
the fault occurred. Press the [FUNC] key to exit.
The fault content will be stored in FU2-01 through
FU2-05 when the [RESET] key is pressed. For
more detail, please refer to Chapter 7.

[Fault Contents]

Fault (Trip)

Keypad Display

Over-Current 1

OC

Over-Voltage

OV

Emergency Stop
(Not Latched)

BX

Low-Voltage

LV

Ground Fault

GF

Over-Heat on Heat sink

OH

Electronic Thermal Trip

ETH

Over-Load Trip

OLT

Inverter H/W Fault

HW

Output Phase Loss

OPO

Input Phase Loss

COL

Inverter Over-Load

IOLT


Note: There is Fan error, EEP error, CPU2 error, Ground fault

and NTC error for the inverter Hardware Fault. The inverter
will not reset when H/W fault occurs. Repair the fault before
turning on the power.

Note: When multiple faults occur, only the highest-level fault

will be displayed.








This function erases all fault histories of FU2-01 to
FU-05 from the memory.

FU2-07: Dwell Frequency
FU2-08: Dwell Time








This function is used to output torque in an
intended direction. It is useful in hoisting
applications to get enough torque before a

Related Functions: DRV-12 [Fault Display] displays current

fault

status.