Chapter 4 - Parameter Description [DRV]

36









[Freq Mode: ‘I’]










[Freq Mode: V1+’I’]


DRV-05 ~ DRV-07: Step Frequency 1 ~ 3











The inverter outputs preset frequencies set in
these codes according to the multi-function input
terminals configured as ‘Speed-L’, ‘Speed-M’ and
‘Speed-H’. The output frequencies are determined
by the binary combination of P1, P2, P3
configured in I/O-12 to I/O-17. Refer to the
following table for the preset frequency outputs.

Speed 4 through Speed 7 is set in I/O-21~I/O-24.

Binary Combination of P1, P2, P3

Speed-L Speed-M Speed-H

Output

Frequency

Step

Speed

0 0 0

DRV-00

Speed

0

1 0 0

DRV-05

Speed

1

0 1 0

DRV-06

Speed

2

1 1 0

DRV-07

Speed

3

0: ON, 1: OFF














[Step Frequency Output]








DRV-08: Output Current





This code displays the output current of the
inverter in RMS.

DRV-09: Motor Speed



Output Frequency

Freq. Max

4mA

20mA

Reference Freq. Range

Analog Signal
Input (I)

Output Frequency

Freq. Max

0V+4mA

Reference Freq. Range

10V+20mA

Analog Signal
Input (‘V1+I’)

P1-CM

ON

Output Frequency

Time

Time

P2-CM

ON

Time

P3-CM

Time

ON

Speed 3

Speed 0

Speed 2
Speed 1

Related Functions: I/O-12 to I/O-14 [Reference Inputs]

I/O-17 [Filtering Time Constant]

I/O-12 to I/O-14: Set the terminal function of P1, P2, P3

terminal inputs.

I/O-17: Adjust response sensibility of input terminal to

eliminate contact noise.