Chapter 6 - Troubleshooting & Maintenance

98

Period

Inspection

Location

Inspection

Item

Inspection

Daily

1 year

2 year

Inspection Method

Criterion

Measuring

Instrument

Cooling

Sy

stem

Cooling

Fan

Is there any abnormal oscillation

or noise?
Is the connection area loose?

Ο

Ο

Turn OFF the power and turn

the fan by hand.
Tighten the connections.

Must rotate

smoothly.
No fault

Display

Meter

Is the displayed value correct?

Ο Ο

Check the meter reading at

the exterior of the panel

Check the

specified and
management

values.

Voltmeter/

Ammeter etc.

All

Are there any abnormal vibrations
or noise?

Is there any unusual odor?

Ο

Ο

Auditory, sensory, visual
check.

Check for overheat and
damage.

No fault

Motor

Insulation

Resistor

Megger check (between the

output terminals and the ground
terminal)

Ο Undo the U, V and W

connections and tie the motor
wiring.

Over 5MΩ

500V class

Megger

Note: Values in ( ) are for the 400V class inverters.