Chapter 5 - MODBUS-RTU Communication

75

Items

Specifications

Control procedure

Asynchronous communication system

Communication system

Half duplex system

Character system

ASCII (8 bit)

Stop bit length

Modbus-RTU: 1 bit, CMC BUS: 2 bit

Sum check

2 byte

Parity check

None

5.3 Installation


5.3.1 Connecting the communication line
- First connect the 485 GND of MODBUS-RTU communication line to the inverter’s (CM) terminals of

the control terminals.

- Then connect the MODBUS-RTU communication line to the inverter’s (S+), (S-) terminals of the

control terminals.

- Check the connection and turn ON the inverter.
- If the communication line is connected correctly set the communication related parameters as the

following:

- Operate with DriveView if DriveView is operating, if not operate with the Keypad.

DRV-03 [Drive mode] : 3(RS485)
DRV-04 [Freq. mode] : 5(RS485)

I/O-46 [Inv. Number] :1~31 (If more than 1 inverters are connected, be sure to use different numbers
for each inverter)

I/O-47 [Baud-rate] : 9,600 bps (Factory default)
I/O-48 [Lost Mode] : 0 - No action (Factory default)
I/O-49 [Time-Out] : 10 – 1.0sec (Factory default)
I/O-50 [Comm.Prot] : 7 - Modbus-RTU, 0 – CMC BUS


5.3.2 System

configuration

- The number of drives to be connected is up to 31 drives.
- The specification of length of communication line is max. 1200m. To ensure stable communication, limit

the length below 700m.

- Use shielded wire for all control signal wiring.

Thinkpad

RS232/485

Converter

INV.#1

Comm.

Terminal

INV.#2

Comm.

Terminal

INV.#n

Comm.

Terminal

JP1 switch on the
right upper side of
control terminal
block should be
shorted using jumper
to connect a
terminating resistor
at the end inverter
connected.