7 parameter code list – Cleveland Range inverter User Manual

Page 87

Advertising
background image

Chapter 5 - MODBUS-RTU Communication


81

5.7 Parameter Code List


< Common >

Parameter

address

Description

Unit

Read/Write

Data value (HEX)

Note

0000

Inverter model

-

R

7: SV-ACtionMaster

0001 Inverter

capacity

-

R

0: 0.5Hp, 1: 1Hp, 2: 2Hp
3: 3Hp, 4:5Hp, 5: 5.4Hp

0002

Inverter input voltage

-

R

0: 220V class, 1:440V class

0003 Version

-

R

313043: Version 1.0C
353043: Version 5.0C

0004

Parameter write enable

-

R/W

0: Write disable (default)
1: Write enable

0005

Reference frequency

0.01 Hz

R/W

0006 Operation

reference

-

R/W

Bit 0: Stop (R/W)
Bit 1: Forward (R/W)
Bit 2: Reverse (R/W)
Bit 3: Fault reset (W)
Bit 4: Emergency stop (W)

0007

Accel time

0.1 sec

R/W

0008

Decel time

0.1 sec

R/W

0009 Output

current

0.1

A

R

000A Output

frequency

0.01

Hz

R

000B Output

voltage

1

V

R

000C

DC Link voltage

000D Output

power

Not

used

000E Operating

status

-

R

Bit 0: Stop
Bit 1: Forward
Bit 2: Reverse
Bit 3: Fault (Trip)
Bit 4: Accelerating
Bit 5: Decelerating
Bit 6: Speed reached
Bit 7: DC Braking

000F Trip

info

-

R

Bit 0: OC
Bit 1: OV
Bit 2: EXT
Bit 3: BX
Bit 4: LV
Bit 5: Fuse Open
Bit 6: GF
Bit 7: OH

0010

Input terminal info

-

R

Bit 0: FX
Bit 1: RX

Advertising