Chapter 5 - MODBUS-RTU Communication

79

Request for Write

ENQ

Drive No.

CMD

Address

The number of

address to

write

Data

SUM

EOT

05h

“01” ~ “1F” “W”

“XXXX” “1” ~ “8” = n “XXXX…”

“XX”

04h

1 byte 2 bytes

1 byte 4 bytes

1 byte

n * 4 bytes 2 1

Total byte = 12 + n * 4 = max. 44 bytes

Acknowledge Response

ACK

Drive No.

CMD

Data

SUM

EOT

06h

“01” ~ “1F”

“W”

“XXXX…”

“XX”

04h

1 byte

2 bytes

1 byte

n * 4 bytes

2 bytes

1 byte

Total byte = 7 + n * 4 = max. 39 bytes


Negative

Acknowledge

Response

NAK

Drive No.

CMD

Error Code

SUM

EOT

15h

“01” ~ “1F”

“W”

“**”

“XX”

04h

1 byte

2 bytes

1 byte

2 bytes

2 bytes

1 byte

Total byte = 9 bytes

Note) As for Run and Frequency command, when Request for Write and Acknowledge Response is exchanged
between pc and inverter for the first time, previous data is returned. In this case, Request for Write Twice.
From the second time of transmission, the exactly same data will be transmitted

.

Request for Monitor Registration: This is useful when constant parameter monitoring and data
updates are required.


Request for Registration of ‘n’ numbers of Address

ENQ

Drive No.

CMD

The number

of address

to monitor

Address

SUM

EOT

05h

“01” ~

“X”

“1” ~

“XXXX…”

“XX” 04h

1 byte

2 bytes

1 byte

1 byte

n * 4

2 bytes

1 byte

Total byte = 8 + n * 4 = max. 40 bytes


Acknowledge

Response

ACK

Drive No.

CMD

SUM

EOT

06h

“01” ~ “1F”

“X”

“XX”

04h

1 byte

2 bytes

1 byte

2 bytes

1 byte

Total byte = 7 bytes