Chapter 4 - Parameter Description [I/O]

66

or over voltage trip.

[V1-Ext]
Inverter changes its frequency reference source
from keypad to ‘V1’ (analog voltage input) when
this terminal is ON.

[Up, Down]
By using the Up and Down function, the drive can
accelerate to a steady speed and decelerate
down to a desired speed by using only two input
terminals.













[Up/Down Operation]


[3-Wire]
This function is for 3-wire start/stop control.
This function is mainly used with a momentary
push button to hold the current frequency output
during acceleration or deceleration.







[Wiring for 3-Wire Operation, P2 set to ‘3-Wire’]















[3-Wire Operation]


[Ext Trip-A]
This is a normally open contact input. When a
terminal set to ‘Ext Trip-A’ is ON, inverter displays
the fault and cuts off its output. This can be used
as an external latch trip.

[Ext Trip-B]
This is a normally closed contact input. When a
terminal set to ‘Ext Trip-B’ is OFF, inverter
displays the fault and cuts off its output. This can
be used as an external latch trip.

[Open-Loop]
This is used to exchange the control mode of
inverter from PID mode (Close Loop) to V/F mode
(Open Loop).
DRV-03 [Drive Mode] and DRV-04 [Frequency
Mode] are applied when the mode has been
changed.

Note: This function can be used only when the inverter is

stopped.

P1-CM

‘Up’

ON

Output Frequency

Time

Time

P2-CM

‘Down’

ON

Time

FX-CM

ON

Time

Freq.

Max.

FX

RX

P2

CM

P2-CM

ON

Output Frequency

Time

Time

FX-CM ON

Time

RX-CM

ON

Time

Freq.

Max.

Freq.

max.