Cleveland Range inverter User Manual

Page 89

Advertising
background image

Chapter 5 - MODBUS-RTU Communication

83

Parameter

address

Parameter

Code

Description

Default

value

Max. value

Min. value

Unit

Note

620C

FU1 #12

DcSt value

50

200

0

1%

620D

FU1 #13

DcSt time

0

600

0

0.1sec

6214

FU1 #20

Max freq.

5000

40000

4000

0.01Hz

6215

FU1 #21

Base freq.

5000

FU1-20

3000

0.01Hz

6216

FU1 #22

Start freq.

10

1000

10

0.01Hz

6217

FU1 #23

Freq limit

0

1

0

6218

FU1 #24

F-limit Lo.

0

FU1-25

0

0.01Hz

6219

FU1 #25

F-limit Hi.

5000

FU1-20

FU1-24

0.01Hz

621A

FU1 #26

Torque boost

0

1

0

621B

FU1 #27

Fwd boost

50

150

0

0.1%

621C

FU1 #28

Rev boost

50

150

0

0.1%

621D

FU1 #29

V/F pattern

0

2

0

621E

FU1 #30

User freq. 1

1250

FU1-32

0

0.01Hz

621F

FU1 #31

User volt. 1

25

100

0

%

6220

FU1 #32

User freq. 2

2500

FU1-34

FU1-30

0.01Hz

6221

FU1 #33

User volt. 2

50

100

0

%

6222

FU1 #34

User freq. 3

3750

FU1-36

FU1-32

0.01Hz

6223

FU1 #35

User volt. 3

75

100

0

%

6224

FU1 #36

User freq. 4

5000

FU1-20

FU1-34

0.01Hz

6225

FU1 #37

User volt. 4

100

100

0

%

6226

FU1 #38

Volt control

1000

1100

40

%

6227

FU1 #39

Energy save

0

30

0

%

6232

FU1 #50

ETH select

0

1

0

6233 FU1

#51 ethperc 180 250 FU1-52 %

6234 FU1

#52 contperc 120 FU1-51

50

%

6235

FU1 #53

Motor type

0

1

0

6236

FU1 #54

OL level

150

250

30

%

6237

FU1 #55

OL time

100

300

0

0.1sec

6238

FU1 #56

OLT select

0

1

0

6239

FU1 #57

OLT level

200

250

30

%

623A

FU1 #58

OLT time

600

600

0

0.1sec

623B

FU1 #59

Stall prev.

0

7

0

623C

FU1 #60

Stall level

200

250

30

%

Advertising