1.8 Control Terminals

30A 30C 30B

1

MO

2

MG

3

CM

4

FX

5

RX

6

CM

7

BX

8

JOG

9

RST

10

CM

1

P1

2

P2

3

P3

4

VR

5

V1

6

CM

7

I

8

FM

9

S+

10

S-

Wire Size

Terminal Name

Terminal

Screw Size

Screw Torque

(Kgf·cm/lb-in)

Solid Wire (mm

2

)

Stranded Wire (mm

2

)

Stripped

Length (mm)

30A, 30C, 30B

M3

5 / 3.6

2.5

1.5

7

MO, MG, CM, FX, RX ~ S-

M2

4 / 2.9

1.5

1.0

5.5


Type Symbol

Name

Description

P1, P2, P3 Multi-Function Input 1, 2, 3

Used for Multi-Function Input. Default is set to “Step Frequency 1, 2, 3”.

FX

Forward Run Command

Forward Run When Closed and Stop When Open.

RX

Reverse Run Command

Reverse Run When Closed and Stop When Open.

JOG

Jog Frequency Reference

Runs at Jog Frequency. The Direction is set by the FX (or RX) Signal.

BX Emergency

Stop

When the BX Signal is ON Output of Inverter is Turned Off. When Motor uses an
Electrical Brake to Stop, BX is used to Turn Off the Output Signal. When BX
Signal is OFF (Not Turned Off by Latching) and FX Signal (or RX Signal) is ON,
Motor continues to Run.

RST

Fault Reset

Used for Fault Reset.

St

arting Contact Function

Se

lect

CM

Sequence Common

Common Terminal for Contact Inputs.

VR

Frequency Setting Power
(+10V)

Used as Power for Analog Frequency Setting. Maximum Output is +12V, 10mA.

V1

Frequency Reference
(Voltage)

Used for 0-10V Input Frequency Reference. Input Resistance is 20 KΩ

I

Frequency Reference
(Current)

Used for 4-20mA Input Frequency Reference. Input Resistance is 250 Ω

Input signal

Analog frequency setting

CM

Frequency Setting
Common Terminal

Common Terminal for Analog Frequency Reference Signal and FM (For
Monitoring).

Analog

FM-CM

Analog Output
(For External Monitoring)

Outputs One of the Following: Output Frequency, Output Current, Output Voltage,
DC Link Voltage. Default is set to Output Frequency. Maximum Output Voltage
and Output Current are 0-12V and 1mA.

30A
30C
30B

Fault Contact Output

Activates when Protective Function is Operating. AC250V, 1A or less; DC30V, 1A
or less.
Fault: 30A-30C Short (30B-30C Open),
Normal: 30B-30C Short (30A-30C Open)

Output signal

Contact

MO - MG

Multi-Function Output
(Open Collector Output)

Use After Defining Multi-Function Output Terminal.
DC24V, 50mA or less.

RS-485

S+, S-

Communication Port

Communication Port for MODBUS-RTU Communication

!