Cleveland Range inverter User Manual

Page 34

Advertising
background image

Chapter 3 - Parameter List

28

Code

Description

Keypad

Display

Setting Range

Units

Factory

Default

Adj.

During

Run

Page

FU2-24

P Gain
During Speed Search

H 24

0 to 9999

1

100

Yes

53

FU2-25

I Gain
During speed search

H 25

0 to 9999

1

5000

Yes

53

FU2-26 Number of Auto Restart Attempt

H 26

0 to 10

1 0

Yes

FU2-27 Delay Time before Auto Restart

H 27

0 to 60 [sec]

0.1 1.0

[sec] Yes

54

FU2-30 Rated Motor Selection

H 30

0.4 (0.37kW)
0.8 (0.75kW)
1.5 (1.5kW)
2.2 (2.2kW)
3.7

3.7

3.7

3.7 (3.7kW)
4.0 (4.0kW)

-

13

No

54

FU2-31 Number of Motor Pole

H 31

2 to 12

1

4

No

FU2-32

14

Rated Motor Slip

H 32

0 to 10 [Hz]

0.01

No

FU2-33 Rated Motor Current in RMS

H 33

0.1 to 99.9 [A]

1

No

FU2-34

15

No Load Motor Current in RMS

H 34

0.1 to 99.9 [A]

1

No

FU2-36 Motor Efficiency

H 36

50 to 100 [%]

1

14

No

FU2-37 Load Inertia

H 37

0 to 2

1 0

No

54

FU2-39 Carrier Frequency

H 39

1 to 10 [kHz]

1 3

[kHz]

Yes

55

0 (V/F)
1 (Slip Compen)

FU2-40 Control Mode Selection

H 40

2 (PID)

-

0 (V/F)

No 56

0 (I)

FU2-50

16

PID Feedback Signal Selection

H 50

1 (V1)

-

I

0

No

FU2-51 P Gain for PID Control

H 51

0 to 9999

1 3000

Yes

FU2-52 I Gain for PID Control

H 52

0 to 9999

1 300

Yes

FU2-53 D Gain for PID Control

H 53

0 to 9999

1 0

Yes

FU2-54 Limit Frequency for PID Control

H 54

0 to FU1-20

0.01

50 / 60 [Hz]

Yes

56

0 (Max Freq)

FU2-70

Reference Frequency for Accel and
Decel

H 70

1 (Delta Freq)

-

Max frq

0

No 57

0 (0.01 sec)
1 (0.1 sec)

FU2-71 Accel/Decel Time Scale

H 71

2 (1 sec)

-

1 (0.1 sec)

Yes 58

0 (Cmd. Freq)
1 (Acc. Time)

FU2-72 Power On Display

H 72

2 (Dec. Time)

1

0

(Cmd. Freq)

Yes 58

13

The rated motor is automatically set according to the inverter model number. If a different motor is used, set the correct motor parameters.

14

This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct motor parameters.

15

Code FU2-32 and FU2-34 appear only when FU2-40 is set to ‘Slip comp’.

16

Code FU2-50 through FU2-54 appears only when FU2-40 is set to ‘PID’.

Advertising