Chapter 4 - Parameter Description [FU1]


45







These functions are available only when ‘User
V/F’ is selected in FU1-29 [V/F Pattern]. Users
can make the custom V/F pattern by setting four
points between FU1-22 [Starting Frequency] and
FU1-21 [Base Frequency].











[User V/F]


Note: When the ‘User V/F’ is selected, the torque boost of

FU1-26 through FU1-28 is ignored.


FU1-38: Output Voltage Adjustment





This function is used to adjust the output voltage
of the inverter. This is useful when using a motor
that has a lower rated voltage than the main input
voltage. When this is set at 100%, inverter outputs
its rated voltage.












Note: The inverter output voltage does not exceed the main

input voltage, even though FU1-38 is set at 110%.


FU1-39: Energy Save Level





This function is used to reduce the output voltage
in applications that do not require high torque and
current at its steady speed. The inverter reduces
its output voltage after accelerating to the
reference frequency (steady speed). This function
may cause over-current trip due to the lack of
output torque in a fluctuating load.
This function does not work with 0% set point
value.










[When Energy Save Level is set at 20%]


Note: This function is not recommended for a large load or for

an application that need frequent acceleration and
deceleration.

Output Voltage

Output
Frequency

Base Freq.

100%

FU1-31

FU1-30

FU1-34

FU1-33

FU1-35

FU1-37

FU1-36

FU1-32

Output Voltage

Output
Frequency

FU1-21 [Base Freq.]

100%

50%

When set at 50%

Output Voltage

Output
Frequency

Reference Frequency
(Steady Speed)

100%

80%