FT-11(D) Technical Manual, Rev. 1.35 November 2010

Page 29 of 52

8.4. Profibus Option (for FT-11 only)

FT-11 indicators which are equipped with the Profibus option can be connected to a PLC bus as described
below.

Profibus DP V0 & V1

Automatic (96 kbit/s to 12 Mbit/s)

Update rate

Weight data will be updated each 40 ms

Response time on entries

5 ms to 25 ms

8.4.1. Electrical

Connections

The pin configuration of the female 9-pol D-Sub Profibus connector (DB9F) is described in the table below:

Pin no.

Signal

Description

1

2

3

B-Line

Positive RxD / TxD, RS485 level

4

RTS

Request to send

5 GND

Isolated

GND

6

+5 V DC

Isolated +5V output for bus termination

7

8

A-Line

Negative RxD / TxD, RS485 level

9

1

Operation mode LED

2

Status LED

3

Profibus Connector

Housing

Shield

Bus cable shield, connected to Ground

Operation mode LED

State

Indication

Action / Comment

Off

Not on-line /No power

Check power and cable

Green

On-line, data exchange

Flashing Green

On-line, clear

Flashing Red (1 flash)

Setup error

Not supported

Flashing Red (2 flash)

PROFIBUS configuration error

Check GSD file

Status LED

State Meaning
Off

No power or Profibus module is initialising

Green Initialized

Flashing Green

Initialized and diagnostic event is present

Red

There is an exception error

8.4.2. Setup

[0--] Interface Block

[03-] Profibus

This sub-block includes the parameters of the Profibus port.

[032 X ] Data Format

0 : Signed 32 bit integer

1 : Signed 32 bit floating point

[033 XX] Address

The address of the instrument will be entered via numerical keypad. Value range is 1 to 126. After editing
the address it is required to restart the instrument.

The GDS file is available on a CD which is supplied together with the instrument.

After the setup of these parameters and the hardware connection as described above, the data interface can be
used as described in Appendix 5.

Important hint:

During the setup the Profibus output (weight value and status bits) will not be updated.

8.4.3. Data

Structure

See Appendix 5.