Canopen option (for ft-11 only), ] interface block [03-] canopen, Electrical connections – Flintec FT-11D User Manual

Page 31: Setup, 034 x ] data format, 035 xx] address, Data structure

Advertising
background image

FT-11(D) Technical Manual, Rev. 1.35 November 2010

Page 31 of 52

8.6. CANopen Option (for FT-11 only)

FT-11 indicators which are equipped with the CANopen option can be connected to a PLC bus as described
below.

Baud rate

Automatic (10 kbps to 12 Mbps)

Update rate

Weight data will be updated each 40 ms

Response time on entries

5 ms to 25 ms

8.6.1. Electrical

Connections

The pin configuration of the male 9-pol D-Sub ProfiNet connector (DB9M) is described in the table below:

Pin no.

Signal

Description

1

2 CAN_L

3 CAN_GROUND

4

5 CAN_SHIELD

6

7 CAN_H

8

9

Connector

1. Run LED

2. Error LED

3. CANopen Connector

Housing Shield

Run LED

State

Indication

Action / Comment

Off

No power or not initialized

No power or cable broken

Green

On-line, data exchange

Green, flashing

On-line, initializing

Green, single flash

Stopped

Check for hardware damages

Green, flickering

Auto baud rate detection in progress

Red

Exception error

Check EDS file

Error LED

State

Indication

Action / Comment

Off

No error

No power or CANopen module is inizializing

Red, single flash

Warning limit reached

Bus error counter reached or exceeded its warning limit

Red, flickering

LSS

LSS services in progress

Red, double flash

Error count event

A guard (NMT slave or master) or heartbeat event has
occured

Red

Bus off (fatal event)

Bus off

8.6.2. Setup

[0--] Interface Block

[03-] CANopen

This sub-block includes the parameters of the CANopen.

[034 X ] Data Format

0 : Signed 32 bit integer

1 : Signed 32 bit floating point

[035 XX] Address

The address of the instrument will be entered via numerical keypad. Value range is 1 to 127. After editing
the address it is required to restart the instrument.

After the setup of these parameters and the hardware connection as described above, the data interface can be
used as described in Appendix 6.

Important hint:

During the setup the CANopen output (weight value and status bits) will not be updated.

8.6.3. Data

Structure

See Appendix 6.

Advertising
This manual is related to the following products: