To test communication with the central station:

1. Call the central station and tell the operator that you will be testing the

system.

2. Arm the system.

3. Test each of the wireless panic buttons and trip at least one sensor of each

type (fire, intrusion, etc.) to verify that the appropriate alarms are working
correctly.

4. When you finish testing the system, call the central station to verify that the

alarms were received.

Table 31: Sensor/user report codes

Arm or disarm from

Reports as user

Panel or remote handheld touchpad

0

Key fob

1 to 40 (sensor number)

Panel auxiliary panic

41

Panel tamper

42

Panel police panic

43

Panel fire panic

44

Dealer access code

44

Installer access code

45

Master code

46

Access codes 1 to 8

47 to 54

Duress code

55

Two-way voice operation

For the central station operator to initiate an audio session:

1. After the panel has completed reporting the alarm, pick up the CS phone and

press the * button to start the audio session.

2. Press 1 or 0 to speak, 2 for VOX operation, and 3 or 6 to listen.

3. Press 99 to terminate the session.

Note:

Panel voice announcements are silenced during AVM sessions. If the

operator does not terminate the session correctly, panel announcements may not
occur for up to 90 seconds after the operator hangs up.