Appendix A:

Simon XT TableTop Control Panel Installation Manual

75

Function

Programming page
reference

Default setting Required setting

Autoarm

Table 11 on page 39

On

On

Unvacated premises

Table 18 on page 48

On

On

Call waiting

Table 13 on page 41

Off

On if reporting to central
station and customer has call
waiting service

Exit extension

Table 11 on page 39

On

On

Swinger shutdown

Table 16 on page 45

On (one trip)

On (one trip)

Fire alarm verify

Table 16 on page 45

Off

On

Duress/panic code

Table 10 on page 38

Disabled

Disabled

Cross zone

“Cross-zoning” on
page 12

Disabled

Disabled for zones with high
probability of false alarms.

Table 37 below describes nonprogrammable (hard-coded) system operation, as
required to meet ANSI-SIA CP-01, and is provided only for your reference.

Table 37: Non programmable (hard coded) system operation

Function

Operation

Silent exit

All annunciators enabled

Remote arming exit
time and progress
annunciation

All annunciators enabled

Abort annunciation

Enabled

Cancel report
annunciation

Enabled

Recent closing

Enabled (2 minute window)

Exit error

Enabled

Restoration of power

Panel resumes operation in same arming state and disregards alarm
signals from sensors for the first 60 seconds after power restoration

Cancel alarm

Enter code only.

Note: During a two-way voice session, additional alarms will be indicated at the
panel immediately and reported to the Central Station as soon as the session
ends.