Mascot LX Boilers and Water Heaters

Page 9

Table 4. Vent / Air Pipe Sizes

Vent System

Vent System

INTAKE / EXHAUST

Max Equivalent

*

Vent and Air Pipe Length (each)

STANDARD OPTIONAL

Size

2" dia 5.1cm

3"/5" dia 7.6/12.7cm

125

40 ft 12.2m

40 ft 12.2m

Installations in the U.S. require exhaust vent pipe that is PVC or CPVC complying
with ANSI/ASTM D1785 F441 or stainless steel complying with UL1738. Laars
supplies the fi rst section of vent pipe which is 16" of CPVC with each boiler. Installa-
tions in Canada require exhaust vent pipe that is certifi ed to ULC S636.
Intake (air) pipe may be PVC, CPVC, ABS or galvanized pipe.

*

To calculate equivalent length, measure the linear feet of the pipe, and add 5 feet

(1.5m) for each elbow used.

INTAKE AND EXHAUST LENGTH

MAX EQUIV.

MAX EQUIV.

CONCENTRIC MAX EQUIV.

SIZE

VENT

FT.

M VENT

FT.

M VENT

FT.

M

50

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

75

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

100

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

125

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

150

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

175

2"

40

6.1

*

3"

*

150 30.5 3/5"

40

6.1

220

2"

30

4.6

*

3"

*

120 24.4 3/5"

40

6.1

INTAKE / EXHAUST

Max Equivalent Vent and Air Pipe Length (each)

STANDARD 2-PIPE

STANDARD 2-PIPE

OPTIONAL CONCENTRIC

SIZES

DIA.

FT.

m DIA.

FT.

m DIA.

FT.

m

50 - 175

2"

40 12.2

*

3"

* 150 45.7 3/5"

40 12.2

220

2”

30 9.1

*

3”

* 120 36.6 3/5”

40 12.2

Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with
ANSI/ASTM D1785 F441 or stainless steel complying with UL1738. Polypropylene installations require
exhaust vent pipe that is certifi ed to ULC S636.
Intake (air) pipe may be any material that complies with ANSI/ASTM D1785 F441, ABS that complies with
ANSI/ASTM D1527 or galvanized material.
Installer must comply fully with manufacturer's installation instructions, to maintain ANSI Z21.13 safety
certifi cation.
Closet and alcove installations do not allow the use of PVC under any circumstances
To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each
elbow used.
* Must use 2x3 adapter within 1 ft. (30cm) of boiler.

Electrical

Data

Size

Boiler

Volts

Phase Amps

MLX 50

120

Single

1.5

MLX 75

120

Single

1.5

MLX 100

120

Single

1.5

MLX 125

120

Single

1.5

MLX 150

120

Single

1.5

MLX 175

120

Single

2.2

MLX 220

120

Single

2.2


*

Minimum 15A circuit required

* Must use 2x3 adapter within 1 ft. (30cm) of boiler.
Reference the Installation and Operation Manual for more details.

SECTION 3.

Venting and Combustion Air

Laars Mascot LX includes a standard CPVC vent/

combustion air adapter. If field connections require use of

PVC/CPVC vent materials, the installer must use proper

adhesive to join CPVC and/or PVC pipe and fittings.

3.1 Combustion Air

Mascot LX boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with the applicable requirements for

Combustion Air Supply and Ventilation in the National

Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural

Gas and Propane Installation Code, CSA B149.1. All

applicable provisions of local building codes must also be

adhered to.
A Mascot LX unit can take combustion air from the

space in which it is installed, or the combustion air

can be ducted directly to the unit. Ventilation air must

be provided in either case.

3.1.1 Combustion Air from Room

In the United States, the most common requirements

specify that the space shall communicate with the

outdoors in accordance with method 1 or 2, which follow.

Where ducts are used, they shall be of the same cross-

sectional area as the free area of the openings to which

they connect.
Method 1: Two permanent openings, one commencing

within 12" (300mm) of the top and one commencing

within 12" (300mm) of the bottom, of the enclosure

shall be provided. The openings shall communicate

directly, or by ducts, with the outdoors or spaces

that freely communicate with the outdoors. When

directly communicating with the outdoors, or when

communicating to the outdoors through vertical ducts,

each opening shall have a minimum free area of 1

square inch per 4000 Btu/hr (550 square mm/kW) of

total input rating of all equipment in the enclosure.

When communicating to the outdoors through

horizontal ducts, each opening shall have a minimum

free area of not less than 1 square inch per 2000 Btu/

hr (1100 square mm/kW) of total input rating of all

equipment in the enclosure.
Method 2: One permanent opening, commencing

within 12" (300mm) of the top of the enclosure, shall

be permitted. The opening shall directly communicate

with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces

that directly communicate with the outdoors and shall