Mascot LX Boilers and Water Heaters

Page 43

the fastening points on the right side of the control to

remove the hooks from the control panel. To replace

the control repeat the steps above in the reverse order

making sure to connect all wires in the proper location.

Place the appliance in operation following the steps

outlined in

Section 10

.

11.2.3 Ignitor Assembly

The ignitor assembly is a two rod system that consists

of a ground rod and a sense rod. To remove the ignitor

assembly, shut off the 120 Volt power supply to the

appliance. Turn off all manual gas valves connecting the

appliance to the main gas supply line. Remove the front

door of the boiler to gain access to the ignitor assembly.

Remove the two wires connected to the assembly. Then

remove the two bolts connecting the ignitor assembly

to the burner door. Remove and replace the old ignitor

assembly gasket. Reinstall a new ignitor assembly in

the reverse order if the old assembly is determined

defective. Replace gasket if necessary.

11.2.4 Flame Sensor

The flame sensor is a single rod system. To replace the

flame sensor electrode, shut off the 120 Volt power

supply to the boiler. Turn off all manual gas valves

connecting the boiler to the main gas supply line.

Remove the front door of the boiler to gain access to

the flame sensor electrode. Remove the flame sensor

wire from the electrode. Remove the two bolts fastening

the electrode to the boiler top. Remove and replace the

old flame sensor gasket. Reinstall a new flame sensor

electrode in the reverse order if the old electrode is

determined defective.

CAUTION

Igniters and sensors get hot and

can cause burns or injury.

11.2.5 Blower

The combustion air blower is a high-pressure centrifugal

blower with a variable speed motor. Speed of the motor

is determined by the control logic. 120 Volts remain on

to the blower at all times. If a blower change is required,

turn off the 120 Volt power and gas supply to the unit.

Take the front panel off. Disconnect the 120 Volt and

control signal connections from the blower. Disconnect

the bolts connecting the venturi to the blower housing.

Disconnect the fan outlet bolts from the burner door

blower arm. If the fan is determined to be defective

replace the existing fan with a new one reversing the

steps above. Make sure to install all of the required

O-rings and gaskets between the blower arm and the

blower and blower face and venturi flange.

11.2.6 Heat Exchanger Coils

Black carbon soot buildup on the internal surfaces of

the heat exchanger is caused by one or more of the

following; incomplete combustion, combustion air

problems, venting problems and heater short cycling.

Soot buildup or other debris on the heat exchanger may

restrict the flue passages.
If black carbon soot buildup on the heat exchanger is

suspected, disconnect electrical supply to the unit, and

turn off the gas supply by closing the manual gas valve

on the unit. Access the heat exchanger through the

burner at the top of the boiler, and inspect the tubing

using a flashlight and a mirror. If there is a buildup of

black carbon soot or other debris on the heat exchanger,

clean per the following:

CAUTION

Black carbon soot buildup on a dirty heat exchanger

can be ignited by a random spark or flame. To prevent

this from happening, dampen the soot deposits with

a wet brush or fine water spray before servicing the

heat exchanger.

1. Shut off the 120 Volt power supply to the boiler
2. Turn off all manual gas valves connecting the boiler

to the main gas supply line.

3. Disconnect all blower wiring and gas valve piping.
4. Remove the four bolts connecting the blower flange

to the burner flange.

5. Remove the burner assembly from the heat

exchanger.

6. Disconnect the condensate drain line.
7. Attach a longer hose to drain and run to a bucket.
8. Clean the heat exchanger by brushing light

accumulations of soot and debris. Use a brush

with soft bristle (non metal) to avoid damaging the

surface of the heat exchanger tubes or refractory.

CAUTION

Be careful not to damage refractory material located

at top and bottom of heat exchanger.

9. Once the tubes have been brushed clean rinse the

tubes and combustion chamber with a small amount

of water to rinse all of the debris out of the bottom

of the flue collector and into the longer condensate

trap line, which is being diverted into a separate

container.

NOTE: The Warranty does not cover damage caused

by lack of required maintenance, lack of water flow,

or improper operating practices.