LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 17

Advertising
background image

Mascot LX Boilers and Water Heaters

Page 13

Figure 11. Combustion Air and Vent Through Roof.

3.3.2 Side Wall Combustion Air Terminal

The LAARS side wall combustion air terminal, or

concentric terminal (

see Table 5

), must be used when the

heater takes air from a side wall. Consider the following

when installing the terminal (

see Figure 12

):

1. Do not locate the air inlet terminal near a source

of corrosive chemical fumes (e.g., cleaning fluid,

chlorine compounds, etc.)

2. Locate the terminal so that it will not be subject to

damage by accident or vandalism. It must be at least

7 feet (2.1m) above a public walkway.

3. Locate the combustion air terminal so that it cannot

be blocked by snow. The National Fuel Gas Code

requires that it be at least 12 inches (30cm) above

grade, but the installer may determine it should be

higher, depending upon local conditions.

4.

For concentric vent, follow instructions included

with vent kit.

5. Multiple vent kits should be installed such that the

horizontal distance between outlet group and inlet

group is 36" (90cm) minimum.

6. Vent outlet must be no lower than the center of the

air inlet, and must be at least 12" (30cm) away from

the air inlet (see

Figure 10

).

3.3 Locating Vent & Combustion Air

Terminals

3.3.1 Side Wall Vent Terminal

The appropriate Laars side wall vent terminal must be

used. The terminal must be located in accordance with

ANSI Z223.1/NFPA 54 and applicable local codes. In

Canada, the installation must be in accordance with CSA

B149.1 or .2 and local applicable codes. Consider the

following when installing the terminal:
1.

Figure 12

shows the requirements for mechanical

vent terminal clearances for the U.S. and Canada.

2. Vent terminals for condensing appliances or

appliances with condensing vents are not permitted

to terminate above a public walkway, or over an

area where condensate or vapor could create a

nuisance or hazard.

3. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows, gravity

inlets or other openings. Whenever possible, avoid

locations under windows or near doors.

5.

Locate the vent terminal so that it cannot be

blocked by snow. The installer may determine

that a vent terminal must be higher than the

minimum shown in codes, depending upon local

conditions.

6. Locate the terminal so the vent exhaust does not

settle on building surfaces or other nearby objects.

Vent products may damage surfaces or objects.

7. If the boiler or water heater uses ducted combustion

air from an intake terminal located on the same

wall, see

Figure 12

for proper spacing and

orientation.

If the vent termination is located in an area exposed to

high winds, an optional PVC tee (the same diameter as

the vent pipe) may be used. The tee'd vent termination

offers greater protection from wind related operating

issues.

Advertising