LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 44

Advertising
background image

LAARS Heating Systems

Page 40

4. Mascot LX will enter the start sequence. Blower

and pump will energize for pre-purge, then the

ignition sequence starts. After all safety devices

are verified, the gas valve opens. If ignition doesn’t

occur, turn off the Mascot LX, check that there is

proper gas supply. Wait 5 minutes and start the unit

again.

5. Turn Mascot LX on.
6. After placing the appliance in operation, the

Burner Safety Shutoff Device must be tested:

(a) Close gas shutoff valve with burner operating.
(b) Flame will go out and blower will continue to run

for the post purge cycle. One or three additional

attempts to light will follow including pre-purge,

ignitor on, valve/flame on and post purge. Ignition

will not occur as the gas is off. The ignition control

will lockout.

(c) Open gas shutoff valve. Reset the boiler control

by pressing the

RESET

button on the control or

on the display. Restart the appliance. The ignition

sequence will start again and the burner will start.

The appliance will return to its previous mode of

operation.

CAUTION

Should any odor of gas be detected, or if the gas

burner does not appear to be functioning in a normal

manner, CLOSE MAIN SHUTOFF VALVE. Do not

shut off switch. Contact your heating contractor, gas

company, or factory representative.

10.2.2 Boiler Setup and Adjustment

1. Measure the CO

2

in the flue products at high fire.

The Mascot LX can be forced to high fire to allow

for easier setup. Refer to

Section 8

for instructions

on how to access the forced rate menu. The CO

2

readings should be between the range shown in

Table 17

. If the CO

2

is not within the range shown,

adjustments may be made. To adjust the high fire

CO

2

, locate the high fire adjuster screw (see

Figure

26

). Using a 2.5 mm Hex wrench, slowly make

adjustments in 1/16 of a revolution increments

until the CO

2

is within the range identified.

(see

Figure 26

)

2. Measure the CO

2

in the flue products at low fire.

Mascot LX can be forced to low fire to allow for

easier setup. Refer to

Section 8

for instructions on

how to access the forced rate menu. CO

2

readings

should be between the range shown in

Table 17

. If

the CO

2

is not within the range shown, adjustments

may be made. To adjust the low fire CO

2

, locate

the low fire adjuster screw. Using a 4 mm Hex

wrench, slowly make adjustments in 1/16 of a

revolution increments until the CO

2

is within

the range identified. (see

Figure 26

)

3. Repeat steps 1 and 2 to confirm that the CO

2

ranges

are within the required ranges. High and Low

Fire CO2 settings should be approximately equal.

Adjust if necessary.

If any CO2 readings

cannot be adjusted to the

specified ranges (see

Table 17)

, please consult the

factory for further information.

WARNING

Improper adjustment may lead to poor combustion

quality, increasing the amount of carbon monoxide

produced. Excessive carbon monoxide levels may

lead to personal injury or death.

10.3 Shutting Down Mascot LX

1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain Mascot LX and be

sure to also protect building piping from freezing.

All water must be removed from heat exchanger

and condensate trap or else damage from freezing

may occur.

This step to be performed by a qualified service person.

10.4 To Restart Mascot LX

If drained, go back to

Section 10

in this manual for

proper filling and purging, prior to continuing.
1. Turn off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).

7. Set the temperature controller to the desired

temperature setting and switch on electrical power.

8. Burner will go through a prepurge period and

ignitor warm-up period, followed by ignition.