Mascot LX Boilers and Water Heaters

Page 41

GAS TYPE

CO2 (%) RANGE

)

Natural 8.9 __ 9.9
Propane 9.9

__ 10.9

Table 17. CO

2

Range and Pressure Settings.

Figure 26. Adjustment Screws and Settings for CO

2

Manifold

Pressure

Screw

(under

cap)

High-fire

setting

Adjustment Screws on

Gas Valve
Close door first, before

measuring CO2 Range

Low-fire

setting

Note: High and Low Fire CO2 settings

should be approximately equal.