Table 15. Installer Parameters (part 1)

Laars SIT Parameters

Page 1

USER MODE

PARAMETER Description

DEFAULT

Parameter

U000

DHW set point

120 °F

USHWDEM

U001

CH set point

130 ° F

US1SETP

U002

Installer Password

15

USPWD

U003

Display timeout

60 sec

DUI1

U004

Unit temperature (F / C)

° F

DUI2

D00 = dhw Temp

INSTALLER MODE

PARAMETER Description

DEFAULT

Parameter

P01

Service notification months

12

SERVICET

P02

Service notification hours since last service

8760

SERVICERUN

P03

Service notification cycles

500

SERVICEOP

P04

Timeout for service mode

180 secs

* displayed as seconds

TMAXSERV

P06

Cascade address and configuration

-1

CASCADD

P07

Cascade temperature set point

140 ° F

CASCREGSETP

P08

Cascade temperature offset

10 °

F

CASCBLO

P09

Cascade temperature hysteresis from offset

20 °

F

CASCHYS

P11

min time a bic must remain on or off

30 sec

shows 300

CASCMINTONOF

P12

min next on time

60 sec

shows 600

CASCMINTNON

P23

Anti cycling time

30 sec

TANTICY

P24

Anti cycling dropoff temperature on s2

10 °F

ANTICYDROF

P25

0-10V to Power (fan speed)

Enabled

FUNCFLAG

P26

0-10V to outlet setpoint

Disabled

FUNCFLAG

P27

Alarm contact configuration

Enabled

Enabled = NO / Disable

FUNCFLAG

P28

DHW demand blocks system pump Enable / Disable

Disabled

FUNCFLAG

P29

System Pump Always On Enable / Disable

Disabled

FUNCFLAG

P30

0-10V Input - Enable / Disable

Enabled

FUNCFLAG

P31

BMS Voltage at Minimum

2 VDC

shows 200

V010AV

P32

BMS Voltage at Maximum

10 VDC

shows 1000

V010BV

P33

On threshold Voltage

1 VDC

shows 100

V010ON

P34

On hysteresis Voltage

.5 VDC

shows 50

V010HYS

P35

BMS Rate at Minimum Voltage

20%

shows 200

V010APOW

P36

BMS Rate at Maximum Voltage

100%

shows 1000

V010BPOW

P37

BMS Temperature Setpoint at Minimum Voltage

70 °F

V010AC

P38

BMS Temperature Setpoint at Maximum Voltage

180 °F

V010BC

P39

Postcirculation time CH pump

30 sec

TPCIRCCH

P40

Postcirculation time DHW pump

30 sec

TPCIRCHW

P41

Postcirculation time System pump

30 sec

TPCIRCSYS

P42

Summer kick CH pump timer

20 sec

SKICKCH

P43

Summer kick DHW pump timer

20 sec

SKICKHW

P44

Summer kick System pump timer

20 sec

SKICKSYS

P45

Delta T Setpoint for CH pump speed control

20 °F

CHPMPSET

P46

Minimum output voltage for CH pump output

3.5 VDC

shows 350

CHPMPMINV

P47

Differential Max Fan Speed for DHW demand

0 RPM

MAXFANHWDIFF

P48

Differential Maximum Fan Speed for CH demand

0 RPM

MAXFANCHDIFF

ANT

ICY

CL

ING &

F

LA

GS

Us

er

set

tin

gs

Ser

vi

ce

C

ont

rol

BMS

CI

RC

U

LA

TI

O

N

PU

M

PS

8.4 INSTALLER Mode

INSTALLER Mode is an extensive set of parameters

that can be changed to suit the individual installation and

should only be accessed by a trained service technician or

installer.

To access the INSTALLER Mode, hold

'Select/OK' and the down ˅ arrow key simultaneously

until U00 is displayed. Press 'Select/OK' again and then

release. Change the value to 15 and then press 'Select/OK'

again. The INSTALLER Mode Parameters will then

be accessible by pressing the Up or Down arrows.

(

See Table 15 and Table 16

)

To change the value of that parameter, press

Select/OK button again. The parameter will blink.

Pressing the Up or Down arrows will increase or

decrease the parameter value. The value will be

confirmed by pressing Select/OK button and the blink