LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 19

Advertising
background image

Mascot LX Boilers and Water Heaters

Page 15

3.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the vent must

extend at least 3 feet (0.9m) above the point at which it

penetrates the roof. It must extend at least 2 feet (0.6m)

higher than any portion of a building within a horizontal

distance of 10 feet (3.0m), and high enough above the

roof line to prevent blockage from snow. When the

combustion air is taken from the roof, the combustion

air must terminate at least 12" (30cm) below the vent

terminal (

see Figure 11

).

3.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a field-

supplied rain cap or an elbow arrangement must be

used to prevent entry of rain water (

see Figure 11

). The

opening on the end of the terminal must be at least 12"

(30cm) above the point at which it penetrates the roof,

and high enough above the roof line to prevent blockage

from snow. When the vent terminates on the roof, the

combustion air must terminate at least 12" (30cm) below

the vent terminal.

3.3.5 Installations in the Commonwealth of

Massachusetts

In Massachusetts the following items are required if the

side-wall exhaust vent termination is less than seven

(7) feet above finished grade in the area of the venting,

including but not limited to decks and porches. From

Massachusetts Rules and regulations 248 CMR 5.08
1. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall vented

gas fueled appliance, the installing plumber or gasfitter

shall observe that a hard-wired carbon monoxide

detector with an alarm battery back-up is installed on the

floor level where the gas appliance is to be installed. In

addition, the installing plumber or gasfitter shall observe

that a battery operated or hard-wired carbon monoxide

detector with an alarm is installed on each additional

level of the dwelling, building or structure served by

the side-wall horizontally vented gas fueled equipment.

It shall be the responsibility of the property owner to

secure the services of qualified licensed professionals for

installation of hard-wired carbon monoxide detectors.

a. In the event that the side-wall horizontally

vented gas fueled equipment is installed in a crawl

space or an attic, the hard-wired carbon monoxide with

alarm and battery back-up may be installed on the next

adjacent floor level.

b. In the event that the requirements of the

subdivision cannot be met at the time of completion of

installation, the owner shall have a period of thirty (30)

days to comply with the above requirements, provided,

however, that during said thirty (30) day period, a

battery operated carbon monoxide detector with an

alarm be installed.
2. Approved Carbon Monoxide Detectors

Each carbon monoxide detector shall comply

with NFPA 720 and be ANSI/UL 2034 listed and IAS

certified.
3. Signage. A metal or plastic identification plate

shall be permanently mounted to the exterior of the

building at a minimum height of eight (8) feet above

grade directly in line with the exhaust vent terminal

for horizontally vented gas fueled heating appliance

or equipment. The sign shall read, in print no less than

one-half (1/2) inch in size: "GAS VENT DIRECTLY

BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS".
4. Inspection

The state or local gas inspector of the side-wall

horizontally vented gas fueled appliance shall not

approve the installation unless, upon inspection, the

inspector observes carbon monoxide detectors and

signage installed in accordance with the provisions of

248 CMR 5.08(2)(a) 1-4.

Advertising