Ladder diagram, mascot lx, 9 ladder diagram, connections, and wiring diagrams – LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 32

Advertising
background image

LAARS Heating Systems

Page 28

Figure 20. Ladder Diagram.

SYSTEM

SENSOR

FLAME

ROD

HI LIMIT

SWITCH

BLDG MGMT

SYSTEM IN

FIELD

INTERLOCKS

AIR

PRESSURE

SWITCH

OUTDOOR

SENSOR

H-X/DHW

SENSOR

TANK

AQUASTAT

COND.

LEVEL

SWITCH

BLOCKED

VENT SW

HI-LO GAS

PRESS SW

WATER

PRESS

SWITCH

X11-7

X2-3

X11-14

X2-6

24

VAC

FLOW

SWITCH

CIRCUIT

BREAKER

ON/0FF

SWITCH

IMPORTANT NOTE

Maximum COMBINED load

on Terminals PWB 4, 6

and 8 shall NOT exceed

5 Amps

PWB

120VAC

NEUTRAL

BLOWER

MAIN CONTROL

120 VAC

24 VAC

PWB-3

PWB-2

PWB-1

X3-4

F3

X11-10

SUPPLY

24VDC

800mA

F1

5A

5A

F2

X3-12

BOILER PUMP

R

R

SYSTEM PUMP

X3-7

X3-6

RELAY

DHW PUMP

RELAY

PWB-4

PWB-6

PWB-8

INLET PROBE

FLUE TEMP

FLUE SAFETY

OPERATING CONTROL

SAFETY LIMIT

H-X/DHW SENSOR

X4-3

X4-9

X4-2

X4-8

X4-1

X3-15,PWB-9

X3-14,PWB-7

X3-5

X3-13,PWB-5

X4-7

FLOW SENSOR

X4-10

X4-4

X4-5

X4-11

X4-12

X11-11

X11-13

X11-5
X11-12

X11-4

X11-6

X11-9

X11-8
X11-1

X11-2

BLOWER

X6-4

FWB1

X6-12

X6-5

X6-13

X6-6

X6-14

X6-7

X6-15

FWB2

FWB3

FWB4

FWB5

FWB6

FWB7

FWB8

FWB9

FWB10

FWB11

X4-4

X4-10

X5-6

X5-3

X5-1

X5-8

X5-5

X1-2

X1-1

X1-3

FWB12

FWB13

FWB14

FWB15

FWB16

FWB17

FWB18

FWB19

0-10 VDC IN

+

-

+

-

0-10 VDC OUT

RATE OUT

GROUND

SHIELD

SHIELD

RS485A

RS485B

CASCADE

SPARE

BY OTHERS

X6-2

X6-10

C

GAS VALVE

X2-1

X2-4
X6-1

X6-9

X11-3

LWCO

X11-7

X11-14

X1-4

X3-10

TR2

T2

CAUTION - HIGH VOLTAGE SPARK WIRE

X4-5

X4-11

X4-12

FLOW SENSOR

MAIN CONTROL

FWB

X3-8

USED ON LABEL H2365000

SHEET 1 OF 2

B

CD 5-22-14

C

INTENDED SIZE:

D

C

B

A

B

C

D

1

2

3

4

REV.

JAB 12/4/13

CJ 12/4/13

ENGR

APPR

4

3

DRAFT

2

APPROVALS

1

JM 5-22-14

C

GRAPHIC CORRECTION

CHECK

DRAFT

ECN

ENGR APPR

APPR

BY LAARS HEATING SYSTEMS CO.

CHANGE:

14-016N-08

REV.

DISCLOSED TO OTHERS FOR MANUFACTURING OR ANY OTHER

.010

REVISIONS

PURPOSE EXCEPT AS SPECIFICALLY AUTHORIZED IN WRITING

N/A

FRACTIONS 1/8"

1

DWG. NO:

FINISH

E23587

TITLE:

SOFTWARE

TOLERANCES ARE:

REPRODUCED, TRANSFERRED TO OTHER DOCUMENTS, USED OR

DECIMALS .XXX

.1

S

N/A

DECIMALS .XX

MATERIAL:

LADDER DIAGRAM, MASCOT LX

.03

DECIMALS .X

DIMENSIONS ARE IN INCHES.

UNLESS OTHERWISE SPECIFIED:

THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN ARE

PROPRIETARY TO LAARS HEATING SYSTEMS CO.AND SHALL NOT BE

ANGLES

DO NOT SCALE DRAWING.

THIRD ANGLE PROJECTION.

SCALE: NONE

7.9 Ladder Diagram, Connections, and Wiring Diagrams

(see

Figure 20 thru Figure 22)