LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 41

Advertising
background image

Mascot LX Boilers and Water Heaters

Page 37

outlet setpoint. The 0-10V signal may also be used to

create a heat demand eliminating the need to supply a

separate “TT call”.

9.3.a External Signal to Control Modulation.
Installer Parameter P25 “0-10V to Power (fan speed)”

– This is the default 0-10VDC configuration in which

the external signal directly corresponds to fan speed

or ‘boiler power’ In this mode, the call is initiated by

the 0-10v input based on Installer Parameters P33 “On

threshold voltage” and P34 “Off hysteresis voltage”.

The modulation power can also be scaled with P35

“BMS rate at minimum voltage” and P36 “BMS rate at

maximum voltage”.

9.3.b External Signal to Control Setpoint.
Installer Parameter P25 “0-10v BMS modulation

control” must be disabled – In this mode the 0-10VDC

input directly controls the boiler's outlet temperature.

Set the parameters using the Installer Parameters P37

“ BMS Temperature setpoint at minimum voltage” and

P38 “BMS temperature setpoint at maximum voltage”

9.3.c External Signal Initiates Heat Demand
In this mode P26 “0-10V BMS Thermostat Demand

Required” must be disabled to eliminate the need for

a separate “TT Call”. This allows a heat demand to be

created every time the 0-10V signal exceeds P33 “BMS

On Volts”. The heat demand will remain until the 0-10V

signal drops below P33 “BMS On Volts” – P34 “BMS

Demand Off Differential Voltage”

9.4 Warm Weather Shutdown

Warm weather shutdown overrides a central heat

call when the outdoor air temperature is greater than

the warm weather shutdown setpoint. Warm weather

shutdown is always active when there is an outdoor

sensor attached to the control. The warm weather

shutdown setpoint can be adjusted in Installer mode,

using P65 “CH outdoor Air Shutdown Temperature” and

P66 “CH Outdoor Air Shutdown Differential”.

9.5 Domestic Hot Water Demand

9.5.a Combi Boiler DHW
For Combi units (MLXC), DHW demand is triggered

by a flow sensor located near the DHW cold water inlet.

When water begins to flow (open faucet, shower, etc.),

the boiler will fire, based on the water temperature

requirements. It may cycle on and off under very low

flow rates. Minimum flow is 0.5 gpm.

9.5.b Boiler only DHW aquastat demand
For Boiler only units (MLXH), an indirect water heater

can be piped-in. An aquastat in the indirect water heater

connected to terminals 7 and 8 will signal demand for

DHW. In this demand mode the boiler will modulate on

the outlet water temperature sensor and use P51 “DHW

setpoint (S1 – Tank) as the setpoint.
9.5.c Boiler only DHW sensor demand
An optional DHW sensor (Laars PN E2337501) can

also be installed in an indirect water heater connected to

terminals 9 and 10 to initiate demand. In this mode the

tank sensor will control demand and modulation based

on the DHW setpoint. In the case of indirect heaters the

boiler will also modulate on the outlet water temperature

sensor and use P51 “DHW setpoint (S1 – Tank) as the

setpoint.
The service person should note the minor wiring

differences on

Figure 22

.

9.6 Domestic Hot Water Priority

DHW priority is used to allow the CH call to be

interrupted when there is a DHW call. This allows

the boiler to use the full capacity to satisfy hot water

demands without interruptions. From the factory the

default settings give priority to DHW for 55 minutes

before switching to satisfy the CH demand. To adjust

navigate to installer parameter P50 “ DHW priority

over CH” and adjust the time as required.

At the end of the DHW priority period the

boiler will switch to CH priority to supply heat to the

building. The boiler remains in this state until P49,

“CH priority time over DHW” expires. To adjust

navigate to installer parameter P49 and adjust the time

as required.

Figure 25. Outdoor Reset Setpoint Temperatures.

Advertising