Page 11

NOTICE

For Category II and IV boilers, be installed so as to

prevent accumulation of condensate; and
For Category II and IV boilers, where necessary,

have means provided for drainage of condensate.

AVIS

les chaudières de catégories II et IV doivent être

installées de façon à empêcher l'accumulation de

condensat; et
si nécessaire, les chaudières de catégories II et IV

doivent être pourvues de dispositifs d'évacuation du

condensat.

NOTICE

The instructions for the installation of the venting

system shall specify that the horizontal portions of

the venting system shall be supported to prevent

sagging; the methods of and intervals for support

shall be specified. These instructions shall also

specify that the venting system:
Category I, II and IV boilers must be installed so

that horizontal sections have a slope of at least ¼

inch per foot (21 mm/m) to prevent accumulation of

condensate; and

For Category II and IV boilers, where necessary,

have means provided for drainage of condensate.

AVIS

Les instructions d'installation du système

d'évacuation doivent préciser que les sections

horizontales doivent être supportées pour prévenir

le fléchissement. Les méthodes et les intervalles

de support doivent être spécifiés. Les instructions

doivent aussi indiquer les renseignements suivants:

les chaudières de catégories I, II et IV doivent

présenter des tronçons horizontaux dont la pente

montante est d'au moins ¼ po par pied (21 mm/m)

entre la chaudière et l'évent; les chaudières de

catégories II et IV doivent être installées de façon à

empêcher l'accumulation de condensat;
et si nécessaire, les chaudières de catégories II et IV

doivent être pourvues de dispositifs d'évacuation du

condensat.

WARNING

All venting must be installed according to this manual

and any other applicable local codes, including but

not limited to, ANSI Z223.1/NFPA 54, CSA B149.1,

CSAB149.2 and ULC-S636. Failure to follow this

manual and applicable codes may lead to property

damage, severe injury, or death.

INSTALLATIONS IN CANADA require the use

of venting material certified to ULCS636. All Gas

vents connected to the Mascot LX, plastic, stainless

steel or otherwise must be certified to this ULC

standard. Appropriate selection of vent material is

very important for proper performance and safe

operation of the Mascot LX.
The flue temperature of the Mascot LX changes

dramatically with changes in operating water

temperature. Therefore, it is necessary to assess the

application of the boiler to determine the required

certified vent class. If the Mascot LX is installed in

an application where the outlet water temperature

exceeds 145°F, and/or installed in a closet, class

IIB or higher vent material is required. If the

system temperatures are unknown at the time of

installation, class IIB or higher venting material is

recommended.
IN CANADA all venting used must meet the

following requirements:
1. ULC-S636 certified and marked
2. The first 3 feet of venting must be accessible for

visual inspection.

3. All components used in the vent system must be

from a certified manufacturer.

4 . Vent system components must not be mixed

with alternate manufacturers certified

components and/or unlisted components.

5 . The venting must be installed according to the

vent manufacturers installation instructions.


The unit’s vent can terminate through the roof, or

through an outside wall.
See

Table 4

to select the appropriate vent pipe

diameter. Vent pipe must pitch upward, toward the vent

terminal, not less than 1/4" per foot, so that condensate

will run back to the Mascot LX to drain. Route vent

pipe to the heater as directly as possible. Seal all

joints and provide adequate hangers as required in the

venting system manufacturer’s Installation Instructions.

Horizontal portions of the venting system must be

supported to prevent sagging and may not have any

low sections that could trap condensate. The unit must

not support the weight of the vent pipe.