SECTION 12.

Troubleshooting

12.1 Sequence of Operation

Mascot LX is a cold start appliance that should start

only on a call for heat from a tank aquastat, room

thermostat, zone valve end switch or other space

temperature control device (flow switch for DHW).
1. Upon a call for heat: (a) the internal pump and

system pump will start; (b) the blower will begin a

short pre-purge.

2. Following the prepurge cycle the direct spark

ignition will spark and will begin a 4 second

trial for ignition. The unit is allowed one or three

ignition retries.

3. The gas valve will then be energized and a reduced

45% rate ignition will occur. The unit will remain

in the reduced rate start-up period for

ten (10) seconds.

4. After the reduced rate start time is over, the

unit will be in normal operation. Firing rate

will modulate based on the heating load via the

temperature controller settings and readings.

5. When the call for heat is complete, or the unit

reaches its setpoint temperature, the gas valve will

close, and the fan will continue to run for its post-

purge. If a pump delay time is used, the pump will

continue to run for the specified amount of time

(adjustable from 0.1 to 10 minutes).

12.2 Short Cycling

Because Mascot LX is a modulating boiler, and its

input will decrease when there is a reduction in heating

load, short cycling is greatly reduced. If the heating

load drops below the minimum input of the boiler for

an extended period, the boiler will have a tendency to

short cycle. This can be a symptom of improper control

or piping layout. When in DHW mode under low load

conditions, the boiler will normally cycle more often,

but should not cycle frequently during call for central

heating.