Figure 10. Minimum Venting Distance.

NOTICE

DO NOT COMMON VENT MASCOT LX UNITS.

Mascot LX units are never permitted to share a

vent with Category I appliances.

AVIS

NE PAS ÉVENT COMMUNE MASCOTTE LX

UNITÉS. Mascotte LX unités ne sont jamais

autorisés à partager un évent Catégorie I avec

les appareils.

3.2.1 About Common Venting

Allowable Polypropylene Vent Manufacturers

/ Trade Names

MFR (model number abbreviated*)

Centrotherm

DuraVent

Selkirk

InnoFlue

PolyPro

Polyflue

Single Wall Pipe

ISVLxxxx

xPPS-x

xPF-xx

Elbow

ESELxxxx

xPPS-E90

xPF-90

PVC adapter

ISAGxxxx

xPPS-AD

xPF-PVC-PF

Notes:

Only the above manufacturers and models have been approved.
Substitutes are not allowed.

Trade Names/Models

"x", "xx" and "xxxx" refer to variations in nominal size. See manufacturer's

catalog for a particular application.
These manufacturers samples have been tested and authorized to safely

operate with Laars equpment.

Contact Polypropylene manufacturer's distributor for complete model

number selection.

Installer must follow Polypropylene manufacturers installation instructions.

Example

Components

Manufacturers materials and models may not be mixed in the same

application.

Table 7. Allowable Vent Manufacturers

INSTALLATION STANDARDS

MATERIAL

UNITED STATES

CANADA

Stainless Steel

UL 1738

Venting must be ULC-S636 certified for use as

PVC, sch 40

ANSI/ASTM D178

venting material. The venting material must be chosen

CPVC, sch 40

ANSI/ASTM F441

based upon the intended application of the boiler.

Polypropylene

UL1738 or ULC-S636

Table 8. Required Exhaust Vent Material.