1 mascot lx heating system pump capacity, 1 central heat system piping – LAARS Mascot LX MLXC 175 MBH - Install and Operating Manual User Manual

Page 22

Advertising
background image

LAARS Heating Systems

Page 18

Mascot LX NATURAL GAS REQUIRED

SIZE

CU FT / HR INPUT RATE.

50

50

75

75

100 100
125 125
150 150
175 175
220 220

TO SIZE PIPING:

Measure linear distance from meter outlet to last boiler. Add total input of all

boilers and divide by 1000 to obtain cu ft / hr required. Add total equivalent

length of fittings used according to Table 6B. Align total length (pipe and

fittings) on left side column of Table 6C with highest cubic feet of gas required.
NOTES: Consult and confirm with Applicable Fuel Gas Code before

beginning work. Verify gas inlet pressure is between 4 and 13 in W.C.

before starting boiler.

Table 11. Natural Gas Required

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING

1/2" 3/4" 1"

LINEAR FEET

90° ELBOW

3.6 4.4 5.2

TEE

4.2 5.3 6.6

Table 12. Equivalent Pipe Lengths.

Table 13. DHW, Performance Data.

SECTION 5.

Pump Capacity

5.1 Mascot LX Heating System

Pump Capacity

Mascot LX's internal pump is sized for a maximum of 30

ft total equivalent pipe. Laars strongly recommends the

unit to be piped in primary/secondary fashion, or use a

low loss header/hydraulic separator.

Please contact Laars for further application details.

Table 11

DHW Performance Data
At various cold water inlet temperatures

Model:

125

50

60

70

GPM

2

100

97

95

3

79

77

75

4

59

58

56

5

48

46

45

Model:

150

50

60

70

GPM

3

95

92

90

4

71

69

68

6

48

46

45

8

36

35

34

Model:

175

50

60

70

GPM

4

83

81

79

5

67

65

63

6

55

54

53

8

42

40

39

Temp Rise F

Inlet Temp F

Temp Rise F

Inlet Temp F

Temp Rise F

Inlet Temp F

125

150

175

SECTION 6.

Water Connections

6.1 Central Heat System Piping

NOTE: This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7kPa)

static pressure at the boiler.

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with this

appliance. Due to expansion and contraction of copper

pipe, consideration should be given to the type of hangers

used. Rigid hangers may transmit noise through the

system resulting from the piping sliding in the hangers.

It is recommended that padding be used when rigid

hangers are installed. Maintain 1" (2.5cm) clearance to

combustibles for hot water pipes.
Pipe the discharge of the pressure relief valve (full size)

to a drain or in a manner to prevent injury in the event of

pressure relief. Minimum fill pressure must be 12psig

(82.7kPa). Install shutoff valves where required by code.

CAUTION

PRV (included) must be installed immediately at boiler

outlet with no valves between. Use PRV adapter pipe

(included) for bottom connections or add PRV directly

to the top of boiler with pipe coupling.

__________________________________________

ATTENTION

PRV (inclus) doit être installé immédiatement à sortie

chaudière avec pas de vannes entre. Utiliser le PRV

tuyau adaptateur (inclus) pour les connexions bas ou

ajouter PRV directement vers le haut de la chaudière

avec raccord de tuyau.

__________________________________________

Suggested piping diagrams are shown on

the following

pages.

These diagrams are meant only as a guide.

Components required by local codes must be properly

installed.

Advertising