Carrier Access Access Bank II SNMP User Manual

Page 138

Advertising
background image

Access Bank II - SNMP Shuts Down for No Apparent Reason

9/24/01

12-17

1. Check the voice cable for a loose connection.

2. Check the voice cable for a broken/open pair.

3. Use Remote Monitor software to run a Self Test Loopback with the Ringback tone. If no

ringing tone is heard at the drop, the ringback generator on the Controller card may be faulty.
Replace the Controller card using the procedure given in the Maintenance section.

12.15 Access Bank II - SNMP Shuts Down for No Apparent

Reason

Internal thermal protectors automatically shut down Access Bank II - SNMP operation if the operat-
ing temperature rises above 140º F (60º C). To correct this problem:

Verify that the Access Bank II - SNMP is properly ventilated to allow for heat dissipation, and reduce
the ambient temperature if necessary. The Access Bank II - SNMP resets automatically when the
temperature is reduced below 104º F (40 C).