Chapter 7 product specification, 1 applicable standards, 2 environmental characteristics – OPTI-UPS MD120L User Manual

Page 104: 3 mechanical characteristics

Advertising
background image

Appendix 2 Toxic or Hazardous Materials or Elements Identification Table 47

47

Chapter 7 Product Specification

This chapter provides UPS product specification.

7.1 Applicable Standards

The UPS has been designed to conform to the following European and international standards:

Table 7-1 Compliance with European and International Standards

Item

Normative reference

General safety requirements for UPS

used in operator access areas

EN50091-1-1/IEC62040-1-1/AS 62040-1-1

Electromagnetic compatibility (EMC)

requirements for UPS

EN50091-2/IEC62040-2/AS 62040-2(C3)

Method of specifying the performance

and test requirements of UPS

EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)

Note: The above mentioned product standards incorporate relevant compliance clauses with generic

IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity

(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).

7.2 Environmental Characteristics

Table 7-2 Environmental Properties

Items

Unit

Requirements

Acoustic noise level at 1

meter

dB

55.0

Altitude of Operation

m

≤1000m above sea level, derate power by 1% per 100m
between 1000m and 2000m

Relative Humidity

%RH 0 to 95%, non condensing

Operating Temperature

0 to 40 deg , Battery life is halved for every 10°C increase

above 20°C

UPS Storage-Transport

Temperature

-20~70

Recommended Battery

Storage Temperature

-20~30 (20°C for optimum battery storage)

7.3 Mechanical Characteristics

Table 7-3 Mechanical Properties

Cabinet Specification

Unit

MD60-10, MD90-15,

MD120-20

MD100-10, MD150-15,

MD200-20

Mechanical Dimension,

W×D×H

mm

600Ч900Ч1600

600Ч900Ч2000

Weight

kg

151

182

Color

N/A

Black

Protection Level,

IEC(60529)

N/A

IP20