1 normal mode, 2 battery mode, 3 auto-restart mode – OPTI-UPS MD120L User Manual

Page 82: 4 bypass mode, 5 maintenance mode

Advertising
background image

Chapter 2 Operations 25

25

 Battery mode

 Auto-Restart mode

 Bypass mode

 Maintenance mode (manual bypass)

 ECO mode

Frequency converters mode

2.2.1 Normal Mode

The UPS inverter power modules continuously supply the critical AC load. The rectifier/charger

derives power from the AC mains input source and supplies DC power to the inverter while

simultaneously FLOAT or BOOST charging its associated backup battery.

2.2.2 Battery Mode

Upon failure of the AC mains input power; the inverter power modules, which obtains power from the

battery, supplies the critical AC load. There is no interruption in power to the critical load upon failure.

After restor

ation of the AC mains input power, the “Normal Mode” operation will continue automatically

without the necessity of user intervention.

Note: UPS can also be started through battery (charged) mode via battery cold start function upon

failure of the AC mains. Therefore, the battery power can be used independently to improve the

utilization rate of UPS.

2.2.3 Auto-Restart Mode

The battery may become exhausted following an extended AC mains failure. The inverter shuts

down when the battery reaches the End of Discharge voltage (EOD). The UPS may be programmed to
“Auto Recovery after EOD” after a delay time if the AC mains recovers. This mode and any delay time
are programmed by the commissioning engineer.

During the process of delay time, the battery will be charged by UPS to prevent any risks to load

equipment from future mains failure.

2.2.4 Bypass Mode

If the inverter overload capacity is exceeded under normal mode, or if the inverter becomes

unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter

to the bypass source, with no interruption in power to the critical AC load.

2.2.5 Maintenance Mode

A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS

becomes unavailable e.g. during a maintenance procedure.

Note: This manual bypass switch is fitted in all UPS modules. Transfer UPS system to bypass mode

for power supply first, then close maintenance bypass switch Q2, followed by Q1 and Q3.

警告

危 险

Warning: Hazard may occur after transferring to maintenance bypass

After UPS being transferred to maintenance bypass, power module and bypass module do not work,

no display on LCD, and input and output terminals as well as N bus are electrically connected.

Advertising
This manual is related to the following products: