7.7 Electrical Characteristics(Bypass Mains Input)

Table 7-7 Bypass Mains Input

Rated

capacity(kVA)

Unit

36

72

120

Rated AC

Voltage

1

Vac

200/208

three-phase four-wire, sharing neutral with the rectifier input and

providing neutral reference for the output

Rated current

A

100@208V

104@200V

200@208V

209@200V

333@208V

348@200V

Overload

125% load, long term

130% load, 1 hour

150% load, 6min

1000% load, 100ms

Superior

protection

bypass line

N/A

Thermal-magnetic breaker, the capacity is 125% of rated current

output. IEC60947-2 curve C

Current rating

of neutral cable

A

1.7×In

Frequency

2

Hz

50/60

Switch time

(between

bypass and

inverter)

ms

Synchronized switch: ≤1ms

Bypass voltage

tolerance

%Vac

Upper limit:+15

Lower limit: -20

Bypass

frequency

tolerance

±2.5, ±5, ±10 or ±20, default: ±10

Synchronization

-Window

Hz

Rated frequency±3Hz (selectable from ±0.5Hz~±5Hz)

Note:

1.

Factory setting is 208V. Commissioning engineers can set to 200V.

2.

Factory setting is 50Hz. Commissioning engineers can set to 60Hz. For example, UPS is set to

frequency inverter mode, and then bypass status will be neglected.

7.8 Efficiency

Table 7-8 Efficiency, Loss and Air Exchange

Rated Efficiency (kVA)

Unit

6120kVA

Efficiency

Normal mode(dual conversion)

90

ECO mode

99

Battery discharging efficiency (DC/AC) (battery at nominal voltage 480Vdc and full-rated linear load)

battery mode

90