7 electrical characteristics(bypass mains input), 8 efficiency – OPTI-UPS MD120L User Manual

Page 107

Advertising
background image

50 Chapter 5 Maintenance

50

7.7 Electrical Characteristics(Bypass Mains Input)

Table 7-7 Bypass Mains Input

Rated

capacity(kVA)

Unit

60

90

100

120

150

200

Rated AC

Voltage

1

Vac

380/400/415

three-phase four-wire, sharing neutral with the rectifier input and

providing neutral reference for the output

Rated current

A

91@380V

87@400V

83@415V

136@380

V

130@400

V

124@415

V

151@380

V

144@400

V

138@415

V

182@380

V

174@400

V

166@415

V

227@380

V

216@400

V

207@415

V

302@380

V

288@400

V

276@415

V

Overload

125% load, long term

130% load, 1 hour

150% load, 6min

1000% load, 100ms

Superior

protection

bypass line

N/A

Thermal-magnetic breaker, the capacity is 125% of rated current output.

IEC60947-2 curve C

Current rating

of neutral cable

A

1.7×In

Frequency

2

Hz

50/60

Switch time

(between

bypass and

inverter)

ms

Synchronized switch: ≤1ms

Bypass voltage

tolerance

%Vac

Upper limit: +10,+15or+20, default: +20

Lower limit: -10, -20, -30 or-40, default:-20

(acceptable stable bypass voltage delay: 10s)

Bypass

frequency

tolerance

±2.5, ±5, ±10 or ±20, default: ±10

Synchronizatio

n-Window

Hz

Rated frequency±2Hz (selectable from ±0.5Hz~±5Hz)

Note:

1.

Factory setting is 400V. Commissioning engineers can set to 380V or 415V.

2.

Factory setting is 50Hz. Commissioning engineers can set to 60Hz. For example, UPS is set to

frequency inverter mode, and then bypass status will be neglected.

7.8 Efficiency

Table 7-8 Efficiency, Loss and Air Exchange

Rated Efficiency (kVA)

Unit

10200kVA

Efficiency

Normal mode(dual conversion)

95

ECO mode

99

Battery discharging efficiency (DC/AC) (battery at nominal voltage 480Vdc and full-rated linear load)

battery mode

95