Safety precautions – OPTI-UPS MD120L User Manual

Page 56

Advertising
background image

Safety Precautions

This manual is about the installation and operation of MD Series modular UPS (Hereinafter referred

to as UPS).

Please carefully read this manual prior to installation.

The UPS must be debugged and maintained by the engineer commissioned by the manufacturer or

the agent. Otherwise, human safety may be endangered and the damage of UPS shall not belong to the

warranty scope.

警告

危 险

APPLICABLE STANDARDS

This product complies with CE 73/23 & 93/68 (low voltage safety) and 89/336 (EMC) , and EMC

standards of Australia and New Zealand (C-Tick) , and the following UPS product standards:

*IEC62040-1-1-General and safety requirements for use in operator access area

*IEC/EN62040-2 EMC requirements CLASS C3

*IEC62040-3 Performance requirements and test methods

警告

危 险

WARNING- High earth leakage current

Earth connection is critical before connecting the input supply (include both utility supply and battery).

This equipment must be earthed in accordance with local electrical authority codes of practice.

Earth leakage current exceeds 3.5 mA and is less than 1000 mA.

Transient and steady-state earth leakage currents, which may occur when starting the equipment,

should be taken into account when selecting instantaneous RCCB or RCD devices.

Residual Current Circuit Breakers ( RCCBs) must be selected insensitive to DC unidirectional pulses

( class A ) and transient current pulses ( RCCBs).

Note it that the earth leakage currents of the load will also flow across RCCB or RCD.

警告

危 险

Components that can be maintained by user

All the equipment maintenance and servicing procedures involving internal access need special tools

and should be carried out only by trained personnel. The components that can only be accessed by

opening the protective cover with tools cannot be maintained by user.
This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator
access area. UPS dangerous voltages are present within the battery box. However, the risk of

contact with these high voltages is minimized for non-service personnel. Since the component with

dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of

touching high voltage component is minimized. No risk exists to any personnel when operating the

equipment in the normal manner, following the recommended operating procedures in this manual.

警告

危 险

Battery Voltage Higher Than 400Vdc

All the battery maintenance and servicing procedures involving internal access need special tools or

keys and should be carried out only by trained personnel.

SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED

WITH THIS EQUIPMENT. WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL

VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY LETHAL.

Battery manufacturers supply details of the necessary precautions to be observed when working on,

or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all

times. Particular attention should be paid to the recommendations concerning local environmental

conditions and the provision of protective clothing, first aid and fire-fighting facilities.

Advertising