52 Chapter 5 Maintenance

52

Appendix A Guidebook to Ordering and Selection of MD System

MD series UPS module can be divided into equipment cabinet and power module. For the cabinet

lectotype please refer to the description in fig 6-1.

Fig 6-1 Cabinet Selection

For single power module type please refers to the description in fig 6-2:

Fig 6-2 Power Module Selection

Egg: the requirements of a plant room are given below:

The maximum power supply of the plant room is 60kVA; however, it is expected to be expanded to

200kVA in 3-5 years. Therefore, a 120kVA cabinet and 5 12kVA power module can be purchased to

constitute an uninterrupted 60kVA power system which can be expanded to 120kVA on-line. The order

symbol is:

1 set MD120/12

6 set MU12

Option list:

MD-SNMP card: remote network monitoring card

MD-1600 dust filter: dust screen for 1.6m cabinet

MD-2000 dust filter: dust screen for 2m cabinet

Represents the capacity of a single power module

06 represents 06kVA

12 represents 12kVA

represents a single power module

Represents UPS system capacity/power module

36/6 represents 36kVA/06kVA:

72/12 represents 72kVA/12kVA:

60/6 represents 60kVA/06kVA:

120/12 represents 120kVA/12kVA:

MD represents UPS cabinet