Chapter 1 Installation

10

开关单元

旁路模块

功率模块

配电单元

1.6m cabinet (front view) 1.6m cabinet (back view)

Fig 1-7 UPS Composition Diagram

Table 1-1 UPS Configuration Table

Involved part name

Quantity (Piece)

Note

Cabinet

Switch PDU

1

Standard configuration

Monitoring + bypass

module

1

Standard configuration

Power module

Power module

1~6 or 1~10

Field installation is

required

1.4.4 Operation Space

As UPS has no ventilation grills at either sides, no clearances are required for the sides.

To enable routine tightening of power terminations within the cabinet, it is recommended that

clearance around the front and back of the equipment should be sufficient to enable free passage of

personnel with the doors fully opened.

1.4.5 Front and Back Access

The component layout of the UPS supports front and back access for servicing, diagnosing and

repairing the UPS, thus reducing the space requirement for side access.

1.4.6 Final Positioning

When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS

will remain stationary and stable.

1.4.7 Power Module Installation

The installation position of power module and output distribution module are shown in fig 1-8. the

installation principle of these modules is to installed from bottom to top to prevent inclination of the

cabinet due to high center of gravity .

As is shown in fig 1-8, the installation procedure of power module is as follows:

switch unit

Switch unit

Bypass module

Power module

Distribution unit