4 electrical characteristics (input rectifier) – OPTI-UPS MD120L User Manual

Page 105

Advertising
background image

48 Chapter 5 Maintenance

48

Module type

Unit

MU10

MU15

MU20

Mechanical Dimension,

W×D×H

mm

440Ч590Ч134

Weight

kg

21

22

22

Color

N/A

Black

7.4 Electrical Characteristics (Input Rectifier)

Table 7-4 Rectifier AC input (mains)

Items

Unit

Parameter

Rated AC Input

Voltage

Vac

380/400/415(three-phase and sharing neutral with the

bypass input)

Input voltage range Vac

-20%~+25%, -40 % power derating

Frequency

2

Hz

50/60(range: 40Hz~70Hz)

Power factor

kW/kVA, full load

0.99

THD

THDI%

3

7.5 Electrical Characteristics (Intermediate DC Link)

Table 7-5 Battery

Items

Unit

Parameters

Battery bus

voltage

Vdc

Nominal: ±240V, one-side range: 198V~288V

Quantity of

lead-acid cells

Nominal

40=[1 battery(12V) ] , 240=[1 battery(2V) ]

Float charge

voltage

V/cell(VRLA)

2.25V/cell(selectable from 2.2V/cell~2.35V/cell)

Constant current and constant voltage charge mode

Temperature

compensation

mV/℃/cl

-3.0(selectable from : 0~-5.0, 25℃ or 30℃, or inhibit)

Ripple voltage

% V float

≤1

Ripple current

% C

10

≤5

Equalized

charge voltage

VRLA

2.4V/cell(selectable from : 2.30V/cell~2.45V/cell)

Constant current and constant voltage charge mode

Final

discharging

voltage

V/cell(VRLA)

1.65V/cell(selectable from : 1.60V/cell ~ 1.750V/cell) @0.6C

discharge current

1.75V/cell (selectable from : 1.65V/cell ~ 1.8V/cell) @0.15C

discharge current

(EOD voltage changes linearly within the set range according to

discharge current)

Battery Charge

V/cell

2.4V/cell(selectable from : 2.3V/cell~2.45V/cell)

Constant current and constant voltage charge mode

Battery

Charging Power

Max Current

kW

10%* UPS capacity (selectable from : 0~20%* UPS capacity)

Advertising
This manual is related to the following products: